Number of inputs and outputs | Number of digital outputs: 2 | ||||
---|---|---|---|---|---|
Measuring range |
|
||||
Process connection | threaded connection G 1/8 Internal thread |
System | gold-plated contacts | ||||
---|---|---|---|---|---|
Application | for industrial applications | ||||
Media | compressed air | ||||
Conditionally suitable for | other media on request | ||||
Medium temperature [°C] | 0...60 | ||||
Min. bursting pressure |
|
||||
Pressure rating |
|
||||
Vacuum resistance [mbar] | -1000 | ||||
Type of pressure | relative pressure; vacuum |
Operating voltage [V] | 18...32 DC; (to SELV/PELV) |
---|---|
Current consumption [mA] | < 50 |
Min. insulation resistance [MΩ] | 100; (500 V DC) |
Protection class | III |
Reverse polarity protection | yes |
Overvoltage protection | yes; (< 40 V) |
Power-on delay time [s] | 0.3 |
Integrated watchdog | yes |
Number of inputs and outputs | Number of digital outputs: 2 |
---|
Total number of outputs | 2 |
---|---|
Output signal | switching signal |
Electrical design | PNP |
Number of digital outputs | 2 |
Output function | normally open / closed; (configurable) |
Max. voltage drop switching output DC [V] | 2 |
Permanent current rating of switching output DC [mA] | 100 |
Switching frequency DC [Hz] | < 200 |
Short-circuit protection | yes |
Type of short-circuit protection | yes (non-latching) |
Measuring range |
|
||||
---|---|---|---|---|---|
Set point SP |
|
||||
Reset point rP |
|
||||
In steps of |
|
Switch point accuracy [% of the span] | < ± 0,5 |
---|---|
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) |
Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
Hysteresis deviation [% of the span] | < ± 0,25 |
Long-term stability [% of the span] | < ± 0,05; (per 6 months) |
Temperature coefficient zero point [% of the span / 10 K] | 0,2; (0...60 °C) |
Temperature coefficient span [% of the span / 10 K] | 0,2; (0...60 °C) |
Response time [ms] | < 2.5 |
---|---|
Delay time programmable dS, dr [s] | 0; 0,002...5 |
Parameter setting options | hysteresis / window; normally open / closed; Diagnostic function; switching logic; switch-on/switch-off delay; Damping; Display unit |
---|
Ambient temperature [°C] | 0...70 |
---|---|
Storage temperature [°C] | -25...85 |
Protection | IP 65 |