Complete set of 630kva outdoor power distribution room European-style substation
Main technical parameter text
Serial number Project unit High voltage electrical appliance transformer Low voltage electrical appliance 1 Rated voltage UekV7.2, 126/0.4, 10/0.40.42 Rated capacity SekvA mesh type: 200~1250 Model: 50~4003 Rated current IeA200~630100~30004 Rated breaking current A load switch 400~630AKA combination electric appliance depends on the fuse 5 rated short time
Withstand current (seconds) KA (XS) 20×(2)200~400kvA15~6312.5×(4)400kvA6 rated peak value
Withstand current KA31.5, 50200~400kvA 15×1400kvA 15×17 Rated closing current KA31.5, 5030×18 power frequency
Withstand voltage 1minKA relative to the ground and the same 32, 40 oil immersion: 35/5min30 isolation fracture 34, 48 dry type: 28/5min639 lightning impact KV relative to the ground and the same 60,7575 isolation fracture 75, 857510 noise level dB oil immersion: < 2kV dry type when 55≤300V: <65300, 2.5kV11 protection grade IP23D12 when 600V shape size According to the selected transformer capacity and form, choose different shape size.
Attributes
Product name: European-style box-type substation / box-type substation
Color: support customization
Applicable places: urban public power distribution, high-rise buildings, living quarters, industrial and mining enterprises, oil fields and temporary construction of projects, etc.
Technical term: YB(M)-10/0.4 European style box-type substation
Rated voltage: 10/0.4KV
Technical standard: GB/T 17467-2020
Place of production: Chengdu
Brand Name: Baikong Electric
Function
It has the characteristics of strong complete set, small size, compact structure, safe and reliable operation, convenient maintenance, and mobility. Compared with conventional civil substations, box-type substations with the same capacity usually occupy only 1/10 of the area of conventional substations. ~1/5, which greatly reduces the design workload and construction volume, and reduces the construction cost. In the power distribution system, it can be used in the ring network power distribution system, and can also be used in the dual power supply or radiation terminal power distribution system. It is a new complete set of equipment for the construction and transformation of urban and rural substations.
Features
1. Flexible combination
Due to the compact structure of the European-style box substation, each box constitutes an independent system, which makes the combination method flexible and changeable. We can all adopt box-type, that is, 35kV and 10kV equipment are installed in all boxes to form a full European-style box substation. ; It is also possible to use 35kV equipment for outdoor installation, 10kV equipment and control and protection system box installation, this combination method is particularly suitable for the transformation of the old rural power grid transformation, that is, the original 35kV equipment does not move, only install a 10kV switch box Can meet the unattended requirements.
2. Low investment and quick results
European-style box substation (35kV equipment outdoor layout, 10kV equipment box installation) compared with the same scale integrated substation (35kV equipment outdoor layout, 10kV equipment layout in the indoor high-voltage switch room and central control room) reduce investment by 40%~50%.
3. Small footprint
The main technical parameters
The main technical parameters | |||||
Serial number | name | unit | High-voltage electrical appliances | transformer | Low-voltage electrical appliances |
1 | Rated voltage | KV | 6/10 | 6/0.4 10/0.4 | 0.4 |
2 | Rated Capacity | KVA | 50-1600 | ||
3 | Rated current | A | 200,400,630 | 100-3200 | |
4 | Rated short-circuit breaking current | A | Load switch 400-630 | 15-63KV | |
KA | Combination switch depends on fuse | ||||
5 | Rated short-time withstand current | KA | 16,20(4S) | 15(1S) | |
30(1S) | |||||
6 | Rated peak withstand current | KA | 31,5.50 | 30 | |
63 | |||||
7 | Power frequency withstand voltage (1MIN) | KV | Relatively and alternately 32/42 | 25/35 (oil diffused) | ≤0.3,2 |
Height port 36/48 | 20/28 (dry type) | >0.3,2.5 | |||
8 | Lightning impulse withstand voltage (peak value) | KV | Relatively and alternately 32/42 | 60/75 | |
Isolated port 70/85 | |||||
9 | Cabinet protection level | IP44 | |||
10 | Noise level | ab | 55 | ||
11 | Executive standard | GB/T 17467 "High-voltage and low-voltage prefabricated substation" | |||
DL/T537 "6-35KV box-type substation ordering technical conditions" |