YBW intelligent integrated outdoor substation European box substation
Overview
European-style box-type substations (MV/LV Prefabricated Substations)arrange high-voltage, distribution transformers, low-voltage power distribution devices, and electric energy metering equipment into a compact power distribution device according to a certain circuit plan, with a small footprint.
Use environmental conditions
1. The altitude does not exceed 1000m;
2. The highest ambient temperature should not exceed +40℃, and the lowest should not be lower than -25℃;
The average temperature within a 24-hour period does not exceed +35℃;
3. Outdoor wind speed does not exceed 35m/s;
4. The relative humidity of the air does not exceed 90% (+25℃);
5. The seismic horizontal acceleration is not more than 0.4m/s2, and the vertical acceleration is not more than 0.2m/s2;
6. A place free from fire, explosion, serious pollution, chemical corrosion and severe vibration.
Note: For special conditions of use, please negotiate with our factory when ordering.
Features
1. Advanced technology, safe and reliable
The box body part adopts domestic and foreign leading technology and craftsmanship. The outer shell is generally made of galvanized steel plate. The frame adopts standard container materials and manufacturing techniques. It has good anti-corrosion performance and guarantees no corrosion for 20 years. The inner sealing plate adopts aluminum alloy buckle plate, sandwich Using fireproof and thermal insulation materials, air conditioning and dehumidification devices are installed in the cabinet, the operation of the equipment is not affected by the natural climate environment and external pollution, and it can ensure normal operation in the harsh environment of -40℃~+40℃.
2. High degree of automation
The whole station is intelligently designed. The protection system adopts the integrated automatic device of the substation and is installed in a decentralized manner. It can realize the "four remotes", namely remote measurement, remote signaling, remote control, and remote adjustment. Each unit has independent operation function and relay protection. The function is complete, and the operating parameters can be remotely set, and the humidity and temperature in the box can be controlled to meet the requirements of unattended operation.
3. Factory prefabrication
When designing, as long as the designer makes a design of the main wiring diagram and the equipment outside the box according to the actual requirements of the substation, he can choose the specifications and models of the box substation provided by the manufacturer. The factory construction of the power station shortens the design and manufacturing cycle; on-site installation only requires cabinet positioning, cable connection between cabinets, outgoing cable connection, protection setting verification, transmission test and other work that needs to be debugged. The entire substation is from installation to It only takes about 5 to 8 days to put into operation, which greatly shortens the construction period.
4. Flexible combination
Due to the compact structure of the European-style box substation, each box constitutes an independent system, which makes the combination method flexible and changeable. We can all adopt box-type, that is, 35kV and 10kV equipment are installed in all boxes to form a full European-style box substation. ; It is also possible to use 35kV equipment for outdoor installation, 10kV equipment and control and protection system box installation, this combination method is particularly suitable for the transformation of the old rural power grid transformation, that is, the original 35kV equipment does not move, only install a 10kV switch box Can meet the unattended requirements.
5. Low investment and quick results
European-style box substation (35kV equipment outdoor layout, 10kV equipment box installation) compared with the same scale integrated substation (35kV equipment outdoor layout, 10kV equipment layout in the indoor high-voltage switch room and central control room) reduce investment by 40%~50%.
6. Small footprint
The main technical parameters
The main technical parameters | |||||
Serial number | name | unit | High-voltage electrical appliances | transformer | Low-voltage electrical appliances |
1 | Rated voltage | KV | 6/10 | 6/0.4 10/0.4 | 0.4 |
2 | Rated Capacity | KVA | 50-1600 | ||
3 | Rated current | A | 200,400,630 | 100-3200 | |
4 | Rated short-circuit breaking current | A | Load switch 400-630 | 15-63KV | |
KA | Combination switch depends on fuse | ||||
5 | Rated short-time withstand current | KA | 16,20(4S) | 15(1S) | |
30(1S) | |||||
6 | Rated peak withstand current | KA | 31,5.50 | 30 | |
63 | |||||
7 | Power frequency withstand voltage (1MIN) | KV | Relatively and alternately 32/42 | 25/35 (oil diffused) | ≤0.3,2 |
Height port 36/48 | 20/28 (dry type) | >0.3,2.5 | |||
8 | Lightning impulse withstand voltage (peak value) | KV | Relatively and alternately 32/42 | 60/75 | |
Isolated port 70/85 | |||||
9 | Cabinet protection level | IP44 | |||
10 | Noise level | ab | 55 | ||
11 | Executive standard | GB/T 17467 "High-voltage and low-voltage prefabricated substation" | |||
DL/T537 "6-35KV box-type substation ordering technical conditions" |