TBBL High Voltage 6kV, 10kV Power System Filter Reactive Compensation Package
Product overview
TBBL high voltage filter reactive compensation package is used for 6~ 35kV power system, mainly installed in power, steel, metallurgy, chemical, coal mine, light industry, building materials and harmonic current, absorb the harmonic current generated by nearby harmonic source, inhibit harmonic and eliminate electric harmonic "pollution".
TBBL device is connected in parallel. In addition to filtering, it also provides reactive power to the system and improves the power factor for reactive compensation.
Use environmental conditions
Note: Plateau type and special environmental conditions products can be solved through negotiation
Dielectric level
Rated voltage of device |
Primary circuit of 1min working frequency withstand voltage (RMSM) |
Primary circuit impact withstand voltage [(1.2~5) / 50us peak] |
Secondary circuit 1min working frequency withstand voltage (RMSM) |
6 |
3 2 |
60 |
2 |
10 |
4 2 |
75 |
2 |
3 |
95 |
200 |
2 |
Operative norm
GB 50227-2008
JB/T7111-1993
DL/T 604-1996
Model and meaning
Main technical performance indicators
Capability deviation
The difference between the actual capacitance and rated capacitance is within 0~ + 5% of the rated capacitance.The ratio between the maximum capacitance and the minimum value between any two line terminals of the device shall not exceed 1.02.
Sensory deviation
The allowable deviation of the resistance value is 0 to + 5% at the rated current.
The resistance value per phase does not exceed 2% of the three-phase average.
Overload capability
Steady-state overvoltage
frequency overvoltage UN |
Maximum duration |
Instruction |
1.1 |
Secular |
The highest long-term overvoltage does not exceed 1.10UN |
1.15 |
For 30 m i n in every 24h |
Adjustment and fluctuation of the system voltage |
1.20 |
5min |
Voltage increases at light load |
1.3 |
1min |
Voltage increases at light load |
Steady state overcurrent: long run at RMS no more than 1.1×1.3IN.
Maximum allowable capacity: within the limit of 5.4.1,5.4.2, the total capacity shall not exceed 1.35QN.
Discharge performance: 5s after power off, the voltage on each set of capacitors is below 50V.
Filter efficiency: reach over 85%.
Power factor was increased to above 0.92 after compensation.
Rated capacity and shape dimensions: all according to the user requirements.