1.Introduction
Compact and Lightweight design that is ideal for moving from job site to job site or within your facility.
Portable Indoor Load Banks offers the most robust, high-capacity designs in the industry. It is setting the standard with intelligent operator controls, safety indication layouts, adjustable load step resolution, and lightweight designs. It is the perfect solution for regularly scheduled maintenance testing and commissioning of mission-critical standby emergency power systems.
2.Main features and advantages
3.Technical Parameter of 1000KW dummy load bank testing for generator
Technical parameter | |
AC400-1000kW | |
Rated voltage /Frequency | AC 3phase 4wire 400V/50Hz |
Max load power | Resistor load: 1010kW |
Load step | Resistive load: 13 steps, 1,2,2,5,10,20,20,50,100,200,200,200,200kW |
Power factor | 1 |
Load Tolerance(each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power Supply | External AC380V/50Hz Three phase four wire |
Wire Connection | Load power supply input——Copper bar (star coupling) Control power supply input——Connector bar |
Insulation grade | F class |
Duty cycle | Continuous |
Cooling | Forced air cooling, Horizontal inlet air, Upward cooling |
Transportation | Hoisting, there are lifting lug in top of casing and casters in bottom of load bank |
CasingColor | Grey(RAL7035) |
Dimension | About 1600 mm×2400mm×2100mm(length*width*height) |
Weight | About 1000kg |
Operating Environment Parameter | |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤2500 meters |
Atmospheric Pressure | 86~106kPa |
Main components brand | |
Contactor | Zhengtai |
Fuse | Delixi |
SCM | Infineon |
Alloy resistor | Kaixiang |
Data management software | Kaixiang |