Portable Dummy Load Banks(namely AC load bank for generator testing), with compact and Lightweight design, equip with castors and lifting rings that is ideal for moving from job site to job site or within your facility. Portable Indoor Load Banks offers the most robust, high-capacity designs in the industry. It is setting the standard with intelligent operator controls, safety indication layouts, adjustable load step resolution, and lightweight designs. It is the perfect solution for regularly scheduled maintenance testing and commissioning of mission-critical standby emergency power systems.
Main Features
1. Control mode:(1)local manual control panel (2)remote manual control box (3) remote console (include manual panel and PC control)(4)laptop control
2. Protection function:overvoltage, overcurrent, overheat, over low blowing rate, blower overheat, blower phase sequence reverse protection, smoke alarm etc.
3. Cooling:industrial heavy duty blower, horizon air intake, upwards outlet, low noise.
4. Power consumption components:made by special alloy resistance, high temperature resisting, high heat dissipation capability, high heat stability, no naked light, safety and reliability. Running temperature is 1/3 of rating.
5. Material and coating:the body adopt cold-rolled steel plate that processed by galvanizing corrosion protection, powder coated and spray paint.
6. Integrated & modularization design:easy to installation, maintenance and transportation.
Technical Parameters
AC400-1000kW Intelligent Load Bank | |
Rating Voltage/Frequency | 400VAC/50Hz, 3 phase 4 wire, line voltage 400V, phase voltage 230V |
Rated Load Power | Resistive load: 1000kW |
Installed Capacity | Resistive load: 1010kW |
Load Step | 1,2,2,5,10,20,20,50,100,200,200,200,200kW, min step load: 1kW |
PF(Power Factor) | 1 |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | 400VAC/50Hz, 3 phase 4 wire, 230V 1-phase |
Wire Connection | Load power supply input——Copper bar (star coupling) Control power supply input——Connector-bar |
Insulation | F |
Protection Grade | IP54 |
Way of Working | Continuous Working |
Casing Dimensions and Cooling | about 1600*2400*2100mm (length*width*height) Forced air cooling,Horizontal inlet air,Vertical cooling |
Weight | About 1500kgs/set |
Transportation | Hoisting, there are lifting lug in top of casing |
Casing Color | Grey(RAL7035) |
Operating Environment Parameter | |
Workplace | Outdoor |
Ambient Temperature | -10℃~+50℃ |