1000kva mtu diesel generator set 16V2000G65 engine
Standby Power 50Hz 880KW / 1100KVA
Prime Power 50Hz 800KW / 1000KVA
Generator Ratings
Prime Power (PRP): Prime power is available for an unlimited number of annual hours in variableload application, in accordance with GB/T2820-97 eqv ISO8528 ; A 10% overload capability is availablefor a period of 1 hour within a 12-hour period of operation.
Standby Power Rating (ESP): The standby power rating is applicable for supplying emergency power
for the duration of a utility power interruption. No overload, utility parallel or negotiated outage operation capability is available at this rating.
ENGINE DATA
Manufacturer / Model: MTU/16V2000G65
Air Intake System: Turbo, Air/Air Cooling
Fuel System: Electronic Fuel Injection System
Cylinder Arrangement: 16 in “V”
Displacement: 31.84L
Bore and Stroke: 130*150 mm
Compression Ratio: 16.0
Rated RPM: 1500rpm
Max. Standby Power at Rated RPM: 975KW without fan
Governor Type: ADEC
Alternator Data
Number of Phase: 3
Connecting Type: 3 Phase and 4 Wires, “Y” type connecting
Number of Bearing: 1
Power Factor: 0.8
Protection Grade: IP23
Altitude: 1000m
Exciter Type: Brushless, self-exciting
Insulation Class, Temperature Rise: H/H
Telephone Influence Factor (TIF): 50
THF: 2%
Voltage Regulation, Steady State: ±1%
Alternator Capacity: 1000KVA
Alternator Efficiencies: 95.1%
Air Cooling Flow: 1.614m3/s
Dimension & Weight
Standard Configuration (Open Type)
Overall Size: 4500(mm)×2000 mm ×2300 mm
Weight: 7850 kg