perkins 750KVA silent diesel generator set data
MODEL QSP800
Standby Power(50Hz) 660KW /825KVA
Prime Power(50Hz) 600KW /750KVA
General Features:
Engine ( Perkins 4006-23TAG2A)
Radiator 40OC max,fans are driven by belt, with safety guard 24V charge alternator
Alternator: single bearing alternator IP23,insulation class H/H Absorber
Dry type air filter, fuel filter, oil filter Main line circuit breaker
Standard control panel batteries, rack and cable Ripple flex exhaust pipe, exhaust siphone, flange, muffler User manual
Generator Ratings
Prime Power (PRP): Prime power is available for an unlimited number of annual hours in variable
load application, in accordance with GB/T2820-97(eqvISO8528); A 10% overload capability is available for a period of 1 hour within a 12-hour period of operation.
Standby Power Rating (ESP): The standby power rating is applicable for supplying emergency power
for the duration of a utility power interruption. No overload, utility parallel or negotiated outage operation capability is available at this rating.
ENGINE DATA
Manufacturer / Model: Perkins 4006-23TAG2A,4-cycle
Air Intake System: Turbo, Air/Air cooling
Fuel Injection System: Direct Injection
Cylinder Arrangement: 6 in line
Displacement: 22.921L
Bore and Stroke: 160×190(mm)
Compression Ratio: 13.6
Rated RPM: 1500rpm
Max. Standby Power at Rated RPM: 717KW/975HP
Governor Type: Electronic
Exhaust System
Exhaust Gas Flow(after turbo): 180m3/min
Exhaust Temperature: 430℃
Max Back Pressure: 6.1kPa
Air Intake System
Max Intake Restriction: 3.8kPa
Consumption: 71m3/min
Air Flow: 1200m3/min