perkins 2500kva diesel generator set data
MODEL QSP2500
Standby Power(50Hz) 2000KW /2500KVA
Prime Power(50Hz) 1818KW /2272KVA
ENGINE DATA
Manufacturer / Model: Perkins 4016-61TRG3,4-cycle
Air Intake System: Turbo, Water/Air cooling
Fuel Injection System: Direct Injection
Cylinder Arrangement: 16 in “V”
Displacement: 61.123 L
Bore and Stroke: 160×190(mm)
Compression Ratio: 13.0
Rated RPM: 1500rpm
Max. Standby Power at Rated RPM: 2183KW/2970HP
Governor Type: Electronic
Exhaust System
Exhaust Gas Flow(after turbo): 490m3/min
Exhaust Temperature: 560℃
Max Back Pressure: 4kPa
Air Intake System
Max Intake Restriction: 3.71kPa
Consumption: 175m3/min
Air Flow: 2500m3/min
Fuel System
100%( Prime Power) Load: 205 g/Kw.h
75%(Prime Power) Load: 200 g/Kw.h
50%(Prime Power) Load: 204 g/Kw.h
100%( Prime Power) Load: 454.4 L/h
Alternator Data
Number of Phase: 3
Connecting Type: 3 Phase and 4 Wires, “Y” type connecting
Number of Bearing: 1
Power Factor: 0.8
Protection Grade: IP23
Altitude: ≤1000m
Exciter Type: Brushless, self-exciting
Insulation Class, Temperature Rise: H/H
Telephone Influence Factor (TIF): <50
THF: <2%
Voltage Regulation, Steady State: ≤±1%
Alternator Capacity: 2275KVA
Alternator Efficiencies: 96.5%
Air Cooling Flow: 2.5m3/s