SFL1-63 16A 32A 40A 63A RCCB Residual Current Device Circuit Breaker RCD
type
|
In/A
|
I△n/A
|
Residual Current (I△)Is Corresponding To The Following Breaking Time | ||||
I△n | 2I△n | 5I△n | 5A ,10A ,20A ,50A ,100A ,200A ,500A | ||||
general type |
any value |
any value |
0.3 | 0.15 | 0.04 | 0.04 | Max Break-time |
S type | ≥25 | >0.03 | 0.5 | 0.2 | 0.15 | 0.15 | Max Break-time |
0.13 | 0.06 | 0.05 | 0.04 | Min non-driving time | |||
G type |
any value |
any value |
0.5 | 0.2 | 0.15 | 0.15 | Max Break-time |
0.01 | 0.01 | 0.01 | 0.01 | Min Non-driving time | |||
The general type RCBO whose current I△n is 0.03mA or less can use 0.25A instead of 5I△n |
Type | Tripping current I△/A | ||
AC | 0.5I△n<I△<I△n | ||
A | Lagging Angle | I△n>0.01A | I△n≤0.01A |
0 | 0.35I△n≤I△≤1.4I△n | 0.35I△n≤I△n≤2I△n | |
90 | 0.25I△n≤I△≤1.41I△n | 0.25I△n≤I△≤2I△n | |
135 | 0.11I△n≤I△≤1.4I△n | 0.11I△n≤I△≤2I△n |