6-32amp 230V 3KA SF30LE-32 RCBO Earth Leakage Circuit Breaker
1. Provides comprehensive protection to household and commercail distribution systems
2. Provides protection against over-voltage
3. Equipped with switched neutral and phase pole
4. Effetively protects electric equipment against insulating failure
5. Provides complementary protection against direct contact by human body.
Test procedure | Type | Test current | Inital State | Tripping or Non-tripping Time Limit | Expected Result | Remark |
a | B,C,D | 1.13In | cold | t≤1h | no tripping | |
b | B,C,D | 1.45In | after test a | t<1h | tripping | current in the 5s in the increase of stability |
c | B,C,D | 2.55In | cold | 1s<t<60(In≤32A) | tripping | |
d | B | 3In | cold | t≤0.1s | no tripping | turn on the auxiliary switch to close the current |
C | 5In | |||||
D | 10In | |||||
e | B | 5In | cold | t<0.1s | ture on the auxiliary switch to close the current | |
C | 10In | |||||
D | 50In | |||||
The terminology "cold state"refes to that no load is carried brfore testing at the reference setting temperature |