SCB Dry Type power distribution transformer
Product Overview:
SC(B)9 Series Resin Insulation Dry-type Transformer is made of high-quality silicon steel sheets, cast epoxy resin, and with intelligentized temperature control system, which will alarm and trip when it fault or overheat.
So it is advantageous in safety, low loss, low noise, fire-proof, low partial discharge and high anti short-circuit capacity.
Also it can be connected with computer, to make it centralized management and supervise.
Due to above features, SC(B) Series Resin Insulation Dry-type Transformer widely apply to power supply and distribution system, such as hotel, airport, tall building, commercial center, hospital, resident area, subway, power industrial, ship , offshore drilling platform and so on.
The technical parameter as follows:
1. Rated capacity: 10~2500kVA
2. Rated HV: 6kV to 10 kV
3. Rated LV: 0.4kv
4. Frequency: 50Hz or 60Hz
5. Cooling methods: Three Independent Cooling Fan
6. Tapping Range: ±5% ±2x2.5%
7. Phase: Single Phase or Three Phases
8. Connection Symbol: Yyn0 or Dyn11
9. Insulation level: LI75AC35/LI 0AC5
10. Insulation grade: F grade
Technical data
Type | Rated capacity (KVA) | Connection groupgrade | Voltagecombination(KV) | Noloadloss (W) | loadloss(W) DyYy | No-load current(%) | Short-circuit resistance(%) | ||
HighvoltageTappingrang | eLowvoltage | ||||||||
SC12-30 | 30 | YynO . Dyn11 | 10 6.3 6 | 土5% +2x2.5% +x2.5% | 0.4 | 150 | 710 | 2.3 | 4.0 |
SC12-50 | 50 | 215 | 1000 | 2.2 | |||||
SC12-80 | 80 | 295 | 1380 | 1.7 | |||||
SC12-100 | 100 | 320 | 1570 | 1.7 | |||||
SC12-125 | 125 | 375 | 1850 | 1.5 | |||||
SC(B)12-160 | 160 | 430 | 2130 | 1.5 | |||||
SC(B)12-200 | 200 | 495 | 2530 | 1.3 | |||||
SC(B)12-250 | 250 | 575 | 2760 | 1.3 | |||||
SC(B)12-315 | 315 | 705 | 3470 | 1.1 | |||||
SC(B)12--400 | 400 | 785 | 3990 | 1.1 | |||||
SC(B)12-500 | 500 | 930 | 4880 | 1.1 | |||||
SC(B)12-630 | 630 | 1070 | 5880 | 0.9 | |||||
SC(B)12-630 | 630 | 1040 | 5960 | 0.9 | |||||
SC(B)12-800 | 800 | 1215 | 6960 | 0.9 | |||||
SC(B)12-1000 | 1000 | 1415 | 8130 | 0.9 | |||||
SC(B)12-1250 | 1250 | 1670 | 9690 | 0.9 | |||||
SC(B)12-1600 | 1600 | 1960 | 11730 | 0.9 | |||||
SC(B)12-2000 | 2000 | 2440 | 14450 | 0.7 | |||||
SC(B)12-2500 | 2500 | 2880 | 17170 | 0.7 |
1.working condition
* Device types: indoor type
* Normal environment conditions of use: the elevation not more than 1000 m
* Environmental highest temperature + 40℃, minimum-25 ℃
* The special environment conditions of use: elevation of more than 1000 m
* Environmental highest temperature + 40 ℃, minimum-45 ℃. (when you order details)
* Mounting ambicnt: no corrosive gas, no obvious dirt environment
2.applicable standard
* IEC60076 power transformer
* IEC723 dry power transformer
* GB6450-1986 dry power transformer
* GB/R1094-1996 power transformer
* GB4208-1993 outer shell protect grade(IP code)
All products of the company have passed the national type test like CCC, CQC , CTQC and other
national mandatory product certification, and has a perfect quality, occupational health and
environmental management system certification system. Our products have passed ISO9001, 2000
and other international quality system certification.
None of the dry-type transformers we see today are installed in a separate, tightly enclosed room, as in
the oil-immersed type, but only in a relatively dry and clean room. In addition to this, it is also very convenient
to transport or carry, no matter what kind of transport vehicles, trains, cars or other non-motor vehicles can be,
but it is best to keep the car dry, clean and the product itself in good packaging. Practice has proved that really
good products will always be more and more marketable. As dry-type transformers have very good fire-proof
performance and are easy to install and maintain, they are also used more and more widely Especially in the
modern commercial downtown, residential areas, hospitals, airports, stations, subways, theaters, schools,
public places and other places with high requirements on fire protection.