AVR Controller EA05A
< ±0.5% Regulation
220/380/440 VAC Programmable Input
Rugged Compact Design
With Under Frequency Protection
Soft Start Voltage Ramping
EMI Suppression
Built-in High Capacity 5 Amp Fuse
Specifications:
Sensing & Power Input
Voltage: 220 / 380 / 440 VAC, 1 phase2 wire.
Frequency: 50 / 60Hz selectable
Output:Voltage: Max. 90 VDC @240 VAC input
Current: Continuous 5A
Intermittent: 7A for 10 sec.
Resistance:Min. 12 Ω.Max. 100 Ω
Voltage Regulation: < ± 0.5% (with 4% engine governing).
Voltage Build-up: More then >5 VAC Residual voltage needed
External Volts Adjustment: ± 7% with 1K Ω 1 watt trimmer.
Soft Start Ramp Time: 2 sec.
Unit Power Dissipation: Max. 8 watt
Thermal Drift: 0.03% per °C change in AVR ambient.
Under Frequency Protection: For 60Hz knee point set at 55Hz
Factory Setting: For 50Hz knee point at 45Hz