AC380V 50/60Hz 90KW Built-in Bypass Squirrel-Cage Asynchronous Electric Motor Soft Starter Used in Fan Control can also effectively reduce the starting current and distribution capacity, to avoid capacity investment. Meanwhile, current transformers and contractors are integrated, users do not need to connect them externally.
Parameter description
Start/stop control parameter
Parameter | Description | Range | Factory value |
C000 | Start mode | 0. Voltage ramp 1. Current limiting | 0 |
C001 | Kick voltage | 20~100%Ue | 20% |
C002 | Kick time | 0~2000mS | 0 |
C003 | Initial voltage | 25~100%Ue | 30% |
C004 | Ramp time | 0~60S | 10 |
C005 | Current limiting | 100~500%Ie | 350% |
C006 | Second-start permission | 0~60S | 0 |
C007 | Stop time | 0~60S | 0 |
C008 | Stop final voltage | 25~60% Ue | 25% |
C009 | Start time delay | 0-----250S | 0 |
C010 | Second current limiting | 150~500%Ie | 400% |
C011-C016 | Undefined parameter | 0-9999 | 0 |
Protection parameter menu
Parameter | Description | Range | Factory value |
C100 | Rated current of motor | 15~9999 | -- |
C101 | Overcurrent protection | 100~500%Ie | 150% |
C102 | Overcurrent time | 1~60S | 1 |
C103 | Current imbalanced protection | 10~100% | 70% |
C104 | Current imbalanced time | 1-60S | 1 |
C105 | Overload protection class | 10A, 10, 15, 20, 25, 30, OFF | 20 |
C106 | SCR protection | 0. On 1. Off | 0 |
C107 | Phase sequence detection | 0. On 1. Off | 0 |
C108 | Frequency protection setting | 0. 50HZ 1. 60HZ | 0 |
C109 | Start time limit | 0~120 | 80 |
C110 | Motor wiring type | 0-external wiring 1-internal wiring 2-undefined (internal-wiring direct start) | 0 |
C111-C116 | Undefined parameter | 0-9999 | 0 |
Port setting parameter menu
Parameter | Description | Range | Factory value |
C200 | Control selection |
Keyboard and communication control Note: the above is available when double contacts are connected |
0 |
C201 | D1 input mode | 0,Fault clearance 1,Urgent input | 0 |
C202 | Programmable relay output | 0,Full voltage output 1,Start course output 2,Soft stop course output 3,Fault output | 1 |
C203 | Relay output delay | 0—250s | 0 |
C204 | Communication address | 1~32 | 1 |
C205 | Baud rate | 0. 1200 1. 2400 2. 4800 3. 9600 4. 19200 | 3 |
C206 | Undefined parameter | 0-9999 | 0 |
C207 | Undefined parameter | 0-9999 | 0 |
C208 | Analog output mode | 0. Average current1(0-200Ie)% 1. Average current2(0-400Ie)% Note: Ie is motor’s rated current | 0 |
C209-C213 | Undefined parameter | ||
C214-C216 | Analog current correction parameter | -------- | --- |
Features
★ Various start-up mode
User can select current-limit starting mode or voltage ramp starting mode. In order to meet site requirements in maximum extent and to achieve the best start effect, you can also impose a programmable jump starting and starting current-limit under each mode.
★ High reliability
High-performance microprocessor makes digital processing on control system, it avoids excessive adjustment on analog lines and achieves excellent accuracy and speed of execution.
★ Strong anti-jamming performance
All external control signals use Photoelectric isolation and set a different anti-noise level. It fits for special industrial environment application..
★ Easy adjustment method
With wide application range of control system, easy and intuitive adjustment. Through a variety of function options to match different types of control object.
★ Optimized structure
Unique compact design of internal structure, particularly user-friendly make it integrated into existing system. It saves costs of current transformer and bypass contactor costs for users.
★ Adaptive power frequency
Power frequency 50/60 Hz, adaptive function, user-friendly.
★ Analog output
4-20mA current output function, user-friendly
★ MODBUS-RTU Communication
During network communications, it can connect up to 32 devices. Users can achieve the purpose of automatic communication by setting baud rate, communication address. The setting range of communication address is 1-32, The factory value is 1. The setting range of communication address is 0,2400; 1,4800; 2,9600; 3,19200. The factory value is 2 (9600).
★ Improved protection function
A variety of motor protection functions (Such as over-current, input/output default phase, thyristor short circuit, overheat protection, leakage detection, electronic thermal overload, internal contactor fault, phase current imbalance, etc.) ensures that motor and soft starter will not be damaged in case of failure or malfunction.
★ Easy to maintain
Monitoring signal coding system consists of four digital display, which monitors system equipment's working conditions, while providing rapid fault diagnosis.
Conditions Of Usage
Control Power | AC110V--AC220V±15% 50/60Hz |
Input Power | AC380V±15% |
Rated Current | 18A--630A |
Adaptive Motor | Squirrel-cage three-phase asynchronous motor |
Start Mode | 1) Current-limiting start; 2) Voltage ramp start; 3) Kick start + current-limiting start; 4) Kick start + voltage ramp start; |
Stop Mode | 1,Soft Stop; 2,Free Stop; |
Digital Input | 1.8KΩ,+15V |
Starting Times | It is recommended not to exceed 10 times per hour. |
Function | 1,Over-heat protection for soft starter; 2,Protection for too long starting time; 3,Input open phase protection; 4,Output open phase protection; 5,Unbalanced three-phase protection; 6,Running over current protection; 7,Running overload protection; 8,Phase error protection; |
Protection Class | IP00,IP20 |
Cooling Pattern | Natural wind cooling |
Place to be used | Indoor location with good ventilation free from corrosive gas and conductive dust. |
Enviroment Condition | Below 2000M. It have to rise the rate power when the altitude is more than 2000M. Ambient Temperature -25+45°C Ambient Humidity 95%(20°C±5°C) |
Connection Diagram
Dimension
Model | G | H | I | K | L | M | E | D | A/B/C |
NKS200-075--160 | 285 | 450 | 305 | 240 | 390 | 9 | 170 | 158 | 50 |
Maintenance
1. Dust: If too much dust, it will reduce the insulation level of the soft starter, even causes the soft starter does not work.
Brush the dust with clean and dry brush.
Remove dust with compressed air machine.
2. Condensation: If condensation, it will reduce the insulation level of soft starter, even causes the soft starter does not work.
(1) Blow it with a hair dryer or electric stove.
(2) Bring it to power distribution room for dehumidification.
3. Regularly check components' intact. Whether it can work properly.
4. Check soft starter' cooling channel, ensure they are not clogged by dirt and dust.
Before maintenance checking, it has to cut off all power in the line side of soft starter.