TSTLP® IP65 Iimp 25kA / 50kA / 100kA 100kA Equipotential Bonding Connector / Isolating Spark Gaps (ISG) for Equipotential Bonding Lightning Protection (Spark Gap Arrester for Cathodic Protection), especially for the separated earthing systems connection.
TSTLP® Model Number | TS-ISG25 | TS-ISG50 | TS-ISG100 |
Lightning impulse current (10/350µs) [Iimp] | 25kA | 50kA | 100kA |
Nominal discharge current (8/20µs) [In] | 100kA | 100kA | 100kA |
Rated power-frequency withstand voltage (50 Hz) [UW/AC] | 300V | 300V | 300V |
100% Lightning impulse sparkover voltage [Urimp] | ≤1.5kV | ≤1.5kV | ≤1.5kV |
Power frequency sparkover voltage (50 Hz) [Uaw] | ≤ 400V | ≤ 400V | ≤ 400V |
Operating temperature range [TU] | -40°C ~ +80°C | -40°C ~ +80°C | -40°C ~ +80°C |
Relative Humidity | ≤ 95% (25 °C) | ≤ 95% (25 °C) | ≤ 95% (25 °C) |
Degree of protection | IP65 | IP65 | IP65 |
Enclosure material | Black Thermoplastic UL94-V0 | Black Thermoplastic UL94-V0 | Black Thermoplastic UL94-V0 |
Connection | Rd 10mm | Rd 10mm | Rd 10mm |
Material (connection) | Copper / Stainless Steel | Copper / Stainless Steel | Copper / Stainless Steel |
Compliance | CE(EMC, LVD) & RoHS | CE(EMC, LVD) & RoHS | CE(EMC, LVD) & RoHS |
INSTALLATION INSTRUCTION
TS series Isolating Spark Gap is applied for in-doors & out-doors,in damp rooms as well as underground installation for lightning equipotential bonding / grounding |
TS Series Isolating Spark Gap INSTALLATION DIAGRAM (for reference)
|
WARNING:
|
Real Installation from one of our clients:
PDF Catalog Download - TSTLP Isolating Spark Gap.p...
Tag: Isolating Spark Gap, Lightning Equipotential Bonding, Equipotential Bonding