24v / 48v / 60v / 120v / 220v / 230v Type 3 Transient Surge Suppressor
TS-230M5RM Class III transient surge suppressor is designed as per IEC 61643-11 to install at LPZ 1-2 or higher as fine protection for electronic devices. e.g. icebox, air conditioner, photocopy, communication equipment, network equipment... various power supply system
Relative 150Vdc / 600Vdc / 750Vdc / 1000V DC Surge Protection Device for photovolatic protection.
Model No. | TS-230M5RM | TS-120M5RM | TS-60M5RM | TS-48M2RM | TS-24M2RM |
Normal a.c. Voltage Un | 230V | 120V | 60V | 48V | 24V |
Rated voltage (max.a.c. continuous voltage) Uc | 320V | 150V | 75V | 60V | 30V |
Rated voltage (max.d.c. continuous voltage) Uc | 320V | 150V | 75V | 60V | 30V |
Normal Current IL | 16A | 16A | 16A | 16A | 16A |
Nominal discharge current (8/20, L-N) In | 3 kA | 2.5 kA | 2.5 kA | 1 kA | 1 kA |
Nominal discharge current (8/20, L+N-PE) In | 5 kA | 5 kA | 5 kA | 2 kA | 2 kA |
Combination wave (L-N) Uoc | 6 kV | 6 kV | 6 kV | 2 kV | 2 kV |
Combination wave (L+N-PE) Uoc | 10 kV | 10 kV | 10 kV | 4 kV | 4 kV |
Voltage protection level(L-N) Up | ≤1.15 kV | ≤0.7 kV | ≤0.5 kV | ≤0.35 kV | ≤0.2 kV |
Voltage protection level(L+N-PE) Up | ≤1.5 kV | ≤1.1 kV | ≤0.85 kV | ≤0.85 kV | ≤0.85 kV |
Response time tA | ≤25ns (L-N); ≤100ns(L+N-PE) | ||||
Max. back up fuse | 16A gL/gG | ||||
Operating temperature range Tu | -40°C...+80°C | ||||
Short-circuit withstand capability at max.backup fuse | 6kArms | ||||
Relative humidity: | ≤95% (25°C) | ||||
Cross-sectional area | 0.5mm2 ~ 6mm2 solid / 4mm2 flexible | ||||
Mounting on | 35mm2 DIN rail | ||||
Enclosure material | Red thermoplastic, UL94-V0 | ||||
Standards | IEC 61643-11; GB 18802.1; YD/T 1235.1 | ||||
Type of remote signalling contact | Break contact | ||||
Switching capacity UN/IN | AC:250V/0.5A DC:250V/0.1A,125V/0.2A,75V/0.5A | ||||
Cross-sectional area for remote signalling contact | Max. 1.5mm2 solid / flexible | ||||
Compliance | CE (LVD, EMC) |
Regularly inspect the operating status, especially after lightning. Once the fuse upstream breaks, or the transient surge suppressor's indicator light displays red, electrician should check/replace the transient surge suppressor.
PDF Catalog Download - TSTLP 24~230V Type 3 SPD.pd...
Tag: transient surge suppressor