TSTLP Field-bus system / thermal resistor / analog signal surge protection device
TSTLP TS-SD Series analog signal surge protection device is for installation at LPZ 0B -2 or higher, protecting the RS422 / RS485 devices against lightning &surge damages, providing coarse and fine protection. Some Custom-made Technical Data available
Model | TS-SD5 | TS-SD24 | |
Nominal voltage | Un | 5V- | 24V- |
Rated voltage (max. continuous voltage) | Uc | 6V(line/line) 160V(line/PG,SG/PG) 6V(line/SG) | 32V(line/line) 160V(line/PG,SG/PG) 32V(line/SG) |
Nominal discharge current (8/20) | In | 10 KA | 10 KA |
Max. discharge current(8/20) | Imax | 20 KA | 20 KA |
Lightning discharge current (10/350) | Iimp | 1KA | 1KA |
Voltage protection level at 4kV( 1.2/50µS) | Up | ≤25V(line/line) ≤800V(line/PG,SG/PG) ≤25V(line/SG) | ≤60V(line/line) ≤800V(line/PG,SG/PG) ≤60V(line/SG) |
Response time | tA | ≤4ns(line/line) ≤20ns(line/PG,SG/PG) ≤4ns(line/SG) | ≤4ns(line/line) ≤20ns(line/PG,SG/PG) ≤4ns(line/SG) |
Max. load current | IN | 100mA | 400mA |
Series impedance per line | R | 2Ω | 1.5Ω |
Capacitance | C | ≤300pF(line/line) | ≤1500pF(line/line) |
≤100pF(line/PG,SG/PG) | ≤100pF(line/PG,SG/PG) | ||
≤300pF(line/SG) | ≤1500pF(line/SG) |
Technical Data Part 2
PDF Catalog Download - TS-SD5-SD24 SPD.pdf
PDF Catalog Download - TS-SC Series SPD.pdf
PDF Catalog Download - TS-ITS-ME SERIES SPD.pdf
PDF Catalog Download - TS-SP Series SPD.pdf
Tag: signal surge protection device, analog signal surge protection