FE-125 IEC60947-2 AC 415V 2P 10KA Minature Circuit Breaker
FE-125 high breaking capacity circuit breaker is used for AC 50/60HZ, single-pole 230V or two, three, four-pole 415V
circuit for protecting the circuit that overload and short circuit may take place. It can be used in lighting and electric motor
distribution system. Mean while it is applicable to an unfrequented switch over the electric apparatus and lighting circuit
under normal condition. Breaking capacity is up to standard of IEC60947-7 10KA.
Specifications
Rated Voltage | 230V/415V AC | |||
Rated Current | 63, 80, 100, 125 A | |||
Characteristic Curve | B,C,D | |||
No of Pole | 1p ,2p,3p,4p | |||
Electrical Life | 6000 times | |||
Mechanical Life | 20000 times (C.O) | |||
Weight | 1P | 2P | 3P | 4P |
150 | 300 | 450 | 600 |
Dimensions
Over current tripping characteristic
Item | Rated Current(A) | Initial State | Test Current | Limited Time | Prospective Result | Starting State |
a | In=63 | Cold State | 1.05In | t ≤1h | Non-tripping | |
In>63 | Cold State | 1.05In | t≤2h | Non-tripping | ||
b | In=63 | Hot State | 1.3In | t<1h | Tripping | The current rise steadily to a fixed value within 5s |
In>63 | Hot State | 1.3In | t<2h | Tripping | ||
c | In≥63 | Cold State | 8In | t≤0.2s | Non-Tripping | |
12In | t<0.2s | Tripping |
Characteristics Curve
Current correction values used at different ambient temperatures
Current correction factor used at different altitudes
Rated Current (A) | Different altitude correction factors | ||
≤2000m | 2000m~3000m | >3000m | |
63,80,100,125A | 1.0 | 0.9 | 0.8 |
Accessories
Application
Item | Code | Application | Standard |
Auxiliary Contacts | OF | Offer auxiliary signal control auxiliary circuit | IEC60947-5-1 GB14048.5 |
Alarm Contacts | SD | Provide an alarm signal when the MCB trip off | IEC60947-2 GB14048.2 |
Shunt Tripper | HDMX | It will let the MCB trip off when the operating voltage exceed the rated voltage by 70%~110% | IEC60947-1 GB14048.1 |
Shunt Tripper + Auxiliary Contact | MX+OF | Remote break the circuit and let the auxiliary contacts control the circuit | IEC60947-1 GB14048.1 |
Over/under Voltage Release | MV+MN | It can peotect the MCB from under / over voltage | IEC60947-2 GB14048.2 |
Technical Data
Working Condition
Temperature: -5℃~+40℃
Altitude : under 2000m
Installation : 35mm DIN rail
Dimensions