surge voltage protection, lightning protection over voltage protection
Technical Parameters | FSP-A | ||||||||||
Rated Operating Voltage Un(V~) | 380V/220V | ||||||||||
Maximum Continuous Operating Voltage Uc(V~) | 275V | 320V | 385V | 385V | 385V | 420V | |||||
Voltage protection Level Up(V~)kV | ≤1.0 | ≤1.2 | ≤1.8 | ≤2.0 | ≤2.2 | ≤2.8 | |||||
Nominal Discharge Current ln (8/20s)kA | 5 | 10 | 20 | 30 | 40 | 60 | |||||
Maximum Discharge Current lmax(8/20s)kA | 10 | 20 | 40 | 60 | 80 | 100 | |||||
Response Time (ns) | <25 | ||||||||||
Test Standard | IEC61643.1, GB18802.1 | ||||||||||
Operating Environment(centigrade) | -40℃ ~+85℃ | ||||||||||
Max Connection Line | 35mm2 hard wire/35mm2 strand wire copper line | ||||||||||
Recommended Connection Line | 16mm2 hard wire/25mm2 strand wire copper line | ||||||||||
Installation | Standard Rail 35mm | ||||||||||
Material of Outer Covering | Burning-proof Nylon |
1. Air-termination system
Metal objects and metal structures that are used to directly receive or bear lightning strikes, such as lightning rods, lightning belts (wires), lightning nets, etc.
2. Down conductor system
The metal conductor that connects the air-termination device to the grounding device.
3. Earth termination system
The sum of the grounding body and the connecting conductor of the grounding body.
4. Earth electrode
A metal conductor buried in the ground that directly contacts the ground. Also called ground electrode. Various metal components, metal facilities, metal pipes, metal equipment, etc. that are in direct contact with the earth can also be used as grounding bodies, which are called natural grounding bodies.
5. Earth conductor
From the grounding terminal of electrical equipment to the connecting wire or conductor of the grounding device, or from the metal object that needs equipotential bonding, the general grounding terminal, the grounding summary board, the general grounding bar, the equipotential bonding bar to the connecting wire or conductor of the grounding device.
6. Direct lightning flash
Lightning that directly strikes actual objects such as buildings, the ground or lightning protection devices.
7. Ground potential counterattack Back flashover
The lightning current passes through the grounding point or grounding system and causes the ground potential of the area to change. The ground potential counterattack will cause the potential of the grounding system to change, which may cause damage to electronic equipment and electrical equipment.
8. Lightning protection system (LPS)
Systems that reduce lightning damage to buildings and installations, including external and internal lightning protection systems.
8.1 External lightning protection system External lightning protection system
The lightning protection part of the exterior or body of a building (structure) usually consists of an air-termination device, a down conductor, and a grounding device to prevent direct lightning strikes.
8.2 Internal lightning protection system
The lightning protection part inside a building (structure) usually consists of an equipotential bonding system, a common grounding system, a shielding system, reasonable wiring, surge protectors, etc., which are mainly used to reduce and prevent lightning current from being caused in the protection space. The electromagnetic effect produced.