Model | FSP-D40 | |||
UC (V DC) | 600/8000V | |||
Max System Discharge Current (8/20 μs) [Imax] | 40kA | |||
Voltage Protection Level [UP] | ≤2.5kV | |||
Integrated Fuse Breaking Capacity/Interrupting Rating | 40kA/600Vdc | |||
Technology | Short-Circuit Interruption (SCI) Overcurrent Protection | |||
Operating Temperature Range [TU] | -40°C to +80°C | |||
Nominal Discharge Current (8/20 μs) [(DC+/DC-) --> PE] [n] | 20kA | |||
Response Time [tA] | <25ns | |||
Operating State/Fault Indication | Green (good)/Red (replace) | |||
Conductor Ratings and Cross-Sectional Area | Min | |||
Mounting | Max | 60/75°C 1.5mm2/14AWG Solid/Flexible | ||
35mm DIN Rail per EN 60715 | 60/75°C 35mm/2AWG Stranded/25mm2/4AWG Flexible | |||
Enclosure Material | UL 94V0 Thermoplastic | |||
Degree of Protection | IP20 | |||
Capacity | 3 Modules, DIN 43880 | |||
Standards Information | IEC 61643-31 Type 2, IEC 61643-1 Class II | |||
Product Warranty | Two Years** | |||
It is a metal oxide semiconductor non-linear resistance with ZnO as the main component. When the voltage applied to its two ends reaches a certain value, the resistance is very sensitive to voltage. Its working principle is equivalent to the series-parallel connection of multiple semiconductor P-Ns. Varistors are characterized by good non-linear characteristics (I=non-linear coefficient α in CUα), large current capacity (~2KA/cm2), low normal leakage current (10-7~10-6A), and low residual voltage (depending on the Due to the working voltage and current capacity of the varistor, the response time to instantaneous overvoltage is fast (~10-8s), and there is no freewheeling.
The technical parameters of varistors mainly include: varistor voltage (ie switching voltage) UN, reference voltage Ulma; residual voltage Ures; residual voltage ratio K (K=Ures/UN); maximum flow capacity Imax; leakage current; response time .
The use conditions of the varistor are: varistor voltage: UN≥[(√2×1.2)/0.7] U0 (U0 is the rated voltage of the industrial frequency power supply)
Minimum reference voltage: Ulma≥(1.8~2) Uac (used under DC conditions)