Note: Range information is very important
The 10m Ultrasonic Level Sensor is a remarkable device. It features a 4 - 20mA output and can automatically control the switch of the water level meter. With a maximum sensing range of 10 meters, it accurately measures water levels, making it highly suitable for various water level monitoring and control applications.
Technical Features:
Structure:
Technical Specifications:
Specs | Value |
Pressure Voltage | 5m, 10m, 15m, 20m, 30m, 40m, 50m, 60m |
Accuracy | 0.5%, 1.0% |
Display | LCD |
Ambient Temperature | Display instrument-20~+60℃ transducer-20~+80℃ |
Medium | liquid and solid |
Analog Output | 4-20mA |
Digital Output | RS485, RS232 (both are optional) |
Power Supply | 24Vdc |
Protection Grade | Display instrument IP65,transducer IP68 |
Probe Type | PVDF, aluminum alloy, ABS, stainless steel 316L, teflon, titanium alloy |
Model Selection:
KUM-A | ||||||
| Measurement Range | |||||
A | 5m | |||||
B | 10m | |||||
C | 15m | |||||
D | 20m | |||||
E | 30m | |||||
F | 40m | |||||
G | 50m | |||||
H | 60m | |||||
| Output Signal | |||||
A | 4-20mA | |||||
| Accuracy | |||||
0.5 | 0.5% | |||||
1.0 | 1% | |||||
| Power Supply | |||||
A | 24Vdc |
| ||||
B | 11~30Vdc |
| ||||
| Probe Type | |||||
A | PVDF | |||||
B | Aluminum alloy | |||||
C | ABS | |||||
D | Stainless steel 316L | |||||
E | Teflon | |||||
F | Titanium alloy |
Applications and Installations:
Common problems and solutions guidance during installation
Fault description | cause of issue | Solution |
Meter does not display, does not work | Wrong power supply Wrong wiring | Check whether the DC24v power supply is correct Check whether the wiring is correct |
The instrument has display, does not work | 1. The level gauge is not aligned with the liquid level or material level | 1. Adjust the alignment direction of the level gauge, and use a spirit level to calibrate and add a plastic tube to the container |
The instrument display is unstable or the measured value has a large deviation | 1. The material level enters the blind spot | 1. Elevate the level meter or prevent the level from being too high |
For the container with the installation port or the probe placed in the round pipe, the length of the flange connection of the 4m, 6m and 8m type level gauge container should be less than 400mm, and the length of the 12m level gauge container should be less than 400mm.
150mm, 15m, 20m, 30m level sensor probes should protrude from the installation port.