KUS640 Ultrasonic Level Sensor With Display fire water system electrical connections management platform
Product overview
KUS640 series intelligent ultrasonic level gauge/level sensor is a level gauge product with on-site display and 4-20mA remote transmission 485 remote transmission launched by our company.
Product Features
Application
KUS640 series is used to indicate and monitor the changes of water pressure/water level value at the installation site, and upload the real-time data to the centralized management platform through the built-in wireless transmission module, which is convenient for users to manage intelligently and centralizedly. It is mainly used in the following industries:
• Fire water system • City water supply
• Sewage treatment • Long-distance heating
• Food industry • Chemical, energy
Technical parameter
Enter | |
Measured variable | liquid level, material level |
Measuring range | 150mm-1000mm(Can be customized according to demand) |
Output | |
Comprehensive accuracy | RS485/4-20mA,±1%FS/ 0.15℃ |
Temperature compensation | -10℃~70℃ |
Vibration effects | < ± 0.05%/g,500Hz in all directions (according to IEC 68-2-64) |
Rated conditions Environmental conditions | |
ambient temperature | -25~+85℃ |
Storage temperature | -40~+85℃ |
Protection class | IP65 ,Complies with EN 60529 |
Electromagnetic Compatibility | EN 61326/A2 Appendix A (2001 ) |
Display and control | |
show | SFTN liquid crystal, green backlight, 5-digit display. |
limit value | Free settings |
Parameter settings | Use 3 buttons |
Unit | mm,The default unit is m. |
Weight | About 1.35kg |
Materials of non-wetted parts | |
Joint | 1NPT,Stainless steel, length 20mm (material and joint specifications can be customized according to customer requirements). |
Electrical connections | Make waterproof connectors, air vent cable entries according to EN 175301-803A |
Measurement period | ≤default 200ms, user set |
Selection Tips: For special requirements, please contact our company and indicate it in the order.
Precautions:
1. If you need to calibrate the instrument, please contact our company. Non-professionals are not allowed to calibrate the instrument.
2. When calibrating the watch, please turn on the watch first, and then calibrate after 1 hour of constant temperature.
Order information
KUS | Model | Output | Range | Describe | |
640B | Product series model | ||||
Custom made | |||||
--- | Independent display header without remote transmission | ||||
4-20mA | 4-20mA remote transmission | ||||
RS485 | RS485 remote transmission (default) | ||||
XXX mm | XXX mmIt means the maximum measurement distance is 1m-50m can be customized | ||||
YYYmm | YYY is the length of the split order cable, the default is 1.2 meters | ||||
KUS | 650 | 4-20mA | 3000mm |