80L 15MPa automatic fire alarm system IG541 safe and pollution-free
Working principle of IG541 fire system:
When any detector in the protection area alarms, the fire alarm signal is transmitted to the fire alarm controller, the sound and light alarm in the protection area room is activated, and all personnel in the protection area should evacuate immediately.
When two detectors in a protection area alarm at the same time, the sound and light alarm outside the protection area is activated, and the fire alarm controller sends a linkage signal to link the fan fire damper, air conditioner and other equipment; the fire alarm controller automatically delays for 30 seconds according to the pre-set time through the gas fire extinguishing controller.
When the delay time is over, the gas fire extinguishing controller sends a signal to release the IG541 mixed gas, starts the solenoid valve on the Shanghai IG541 mixed gas fire extinguishing cylinder to open the selection valve of the corresponding protection area through ammonia, and then opens the container valve on the IG541 gas cylinder to release the IG541 mixed gas to extinguish the fire. After the gas fire extinguishing controller receives the gas release signal fed back by the pressure switch on the main pipeline, it lights up the gas spray indicator light to warn people outside the protection area not to enter the protection area. The IG541 mixed gas will completely flood the entire protection area within the specified time.
During the entire IG541 mixed gas fire extinguishing process, the gas fire extinguishing controller transmits the control panel fault signal and gas release signal to the fire alarm controller.
The IG541 fire extinguishing system has three modes for users to choose: automatic fire extinguishing, emergency electrical manual fire extinguishing, and on-site mechanical fire extinguishing.
Applied range
Heptafluoropropane fire extinguishing agent can extinguish the following fires | The heptafluoropropane fire extinguisher can't put out the fire of the following substances |
|
|
Executive standard | GB 25972-2010 | |||||
System working pressure(20℃时,MPa) | 15 | 20 | ||||
Volume of fire extinguishing agent bottle group(L) | 70 | 80 | 90 | 80 | 82 | 90 |
System injection time(s) | ≤60 | ≤60 | ||||
Filling quantity of extinguishing agent(kg) | 14.77 | 16.88 | 18.99 | 22.49 | 23.05 | 25.3 |
System service temperature(℃) | 0~+50 | 0~+50 | ||||
Minimum fire extinguishing design concentration | 37.5% | 37.5% | ||||
Safe design concentration of manned workplace | ≤43% | ≤43% |
Company introduction:
Guangzhou Rongan Fire Protection Equipment Co., Ltd. is a professional manufacturer of fire protection facilities integrating R&D, production, design and sales services. The company has experts from the national fire protection industry standards committee and a group of professional technical service teams with more than ten years of experience in the fire protection industry, and will spare no effort to provide you with the most intimate and professional comprehensive technical solutions for fire protection engineering products. "Rongxiao" series products produced by the company have passed the national compulsory product certification and the national fixed fire extinguishing system inspection center, with reliable quality and stable performance, and the factory has passed the ISO9001 quality system certification.
Frequently asked questions:
Q1: Are you a manufacturer or a trading company? A1: We are manufacturers.
Q2: How long is the delivery time? A2:10 days, which can be negotiated according to the quantity.
Q3: How to deal with the fault? A3: During the warranty period, we will provide you with a remote emergency plan during working hours. During the free maintenance period, the company will replace spare parts or complete machines that have failed due to defects or quality problems free of charge.