IG541 Fire Extinguishing System 90L Cylinder Factory Direct Quality Assurance Best Price
Working principle of IG541 gas fire extinguishing system
This system has three starting modes: automatic start mode, manual start mode and mechanical emergency operation start mode.
Automatic start mode
The gas fire extinguishing alarm control system is generally equipped with two different types of fire detectors. There are "automatic" and "manual" manual conversion switches on the control host (the conversion switch can also be separated from the host and set outside the protection zone). When it is placed in the "automatic" position, the fire extinguishing system is in automatic state.
When only one detector sends a fire signal, the control host starts the alarm or sound and light alarm to notify the fire, but does not start the fire extinguishing system.
When two detectors send a fire signal, the control host starts the alarm and sound and light alarm, closes the opening of the protection zone, enters the fire extinguishing start delay, and automatically starts the fire extinguishing system after the set delay time is reached.
If it is found that the fire extinguishing system does not need to be started during the spraying delay process, the "emergency stop" button outside the protection zone or on the controller can be pressed to terminate the fire extinguishing command.
Manual start mode
When the switch is in the "manual" position, the fire extinguishing device is in manual state.
In this state, the detector sends a fire signal, and the control host starts the alarm and sound and light alarm to notify the fire, but does not start the fire extinguishing system. At this time, press the "manual start" or "emergency start" button outside the protection zone or on the controller to start the fire extinguishing system.
Note: Whether the controller is in automatic or manual state, pressing the "emergency start" and "manual start" buttons can start the fire extinguishing system.
Mechanical emergency operation start mode
When both automatic and manual starts fail, mechanical emergency operations can be implemented according to the following steps:
1) Manually close the linkage equipment and cut off the power supply;
2) Pull out the "mechanical emergency start safety pin" on the electromagnetic driver of the start bottle of the corresponding protection zone, press the mechanical emergency start button, and the electromagnetic driver opens the start bottle to release the start gas and start the fire extinguishing system.
Executive standard | GB 25972-2010 | |||||
System working pressure(20℃时,MPa) | 15 | 20 | ||||
Volume of fire extinguishing agent bottle group(L) | 70 | 80 | 90 | 80 | 82 | 90 |
System injection time(s) | ≤60 | ≤60 | ||||
Filling quantity of extinguishing agent(kg) | 14.77 | 16.88 | 18.99 | 22.49 | 23.05 | 25.3 |
System service temperature(℃) | 0~+50 | 0~+50 | ||||
Minimum fire extinguishing design concentration | 37.5% | 37.5% | ||||
Safe design concentration of manned workplace | ≤43% | ≤43% |
Company introduction:
Guangzhou Rongan Fire Protection Equipment Co., Ltd. is a professional manufacturer of fire protection facilities integrating R&D, production, design and sales services. The company has experts from the national fire protection industry standards committee and a group of professional technical service teams with more than ten years of experience in the fire protection industry, and will spare no effort to provide you with the most intimate and professional comprehensive technical solutions for fire protection engineering products. "Rongxiao" series products produced by the company have passed the national compulsory product certification and the national fixed fire extinguishing system inspection center, with reliable quality and stable performance, and the factory has passed the ISO9001 quality system certification.
Frequently asked questions:
Q1: Are you a manufacturer or a trading company? A1: We are manufacturers.
Q2: How long is the delivery time? A2:10 days, which can be negotiated according to the quantity.
Q3: How to deal with the fault? A3: During the warranty period, we will provide you with a remote emergency plan during working hours. During the free maintenance period, the company will replace spare parts or complete machines that have failed due to defects or quality problems free of charge.