Specifications
Brand Name :
xingjin
Certification :
CAL,CMA,CNAS,ILAC-MRA,CCC
Place of Origin :
China
MOQ :
2 set system
Price :
negotiation
Payment Terms :
T/T, L/C
Supply Ability :
30000 set system
Delivery Time :
15-20 working days after payment or receipt of L/C
Packaging Details :
Plywood outer box with bubble bag or paper
Filling pressure :
4.2Mpa
Power :
DC24V/1.6A
Standard of examination :
GB25972-2010
Storage pressure :
4.2Mpa
Agent :
Fm200(htc-227ea or heptafluoropropane)
Capacity of cylinder :
90L
Description

Auto Or Mechanical Mode Fm200 Fire Suppression System Pipe Network Type Single Zone


Parameter

NO. Specifications Parameters
4.2Mpa 5.6Mpa
1. Capacity 70l,100l,120l,150l,180l 90l,120l
2. Filling pressure 4.2Mpa 5.6Mpa
3. Filling density ≤950kg/m³ ≤1080kg/m³
4. Discharge time ≤10s ≤10s
5. Power DC24V/1.6A DC24V/1.6A
6. Nitrogen driving device 6.0±1.0Mpa 6.0±1.0Mpa
7. Storage surroundings

Temperature:-10~50℃
Relative humidity:≤97%

Temperature:-10~50℃
Relative humidity:≤97%

8. proportion ≤800m² ≤800m²
9. volume ≤3600m³ ≤3600m³



Description

Fm200 fire suppression is one of the competitive system among the fire suppression systems. Because of its clean and environmentally friendly nature, this system is known by more and more people all around the world. Moreover, fm200 fire suppression system now is considered as the best substitute to halon series.
Fm200 fire suppression system is odorless and tasteless. Besides, it has its standard concentration for putting out a fire. Usually, the concentration reach 9% is enough to protect a occupied protected zone. In some special cases, the concentration will reach 10% and do harm to our human body if it remains in the protected zone for a long seconds. Thus the common concentration of fm200 fire suppression is 9%.


Application

As its name tells, the single zone fm200 fire suppression system is suitable for a big and significant protected zone and several kinds of fire. The proper places for reference:
1. Telecommunication rooms
2. Data and paper archives
3. Switch gear rooms
4. Computer rooms
5. Military applications and cell sites
6. High-tech medical
7. Robotic equipment
8. Telecommunication centers
9. Textile manufacturing
10. Records and data archives
11. Electric utility facilities


Advantages

There are a lot of advantages of this system, and here is going to have a summary for all the customer.
Strong points:
1/ Flexible application in protection zones. As its structure and assembly of other useful components, it can concentrate one very big protection zone with the combination of multiple storage cylinders. Its coverage can be also very small with the system of a single cylinder.
2/ Efficient spraying of gas. One set of pipe network system can make the discharge on average for big zones in less than 10 seconds with the help of the deployment of the pipeline.
3/ Combined distribution system. The most distinctive and flexible advantage of this system is combined distribution system, which will combine multiple rooms in one district or building, and those rooms are with different dimensions or on different floors. Meanwhile, it can help saving money based on the original by the least and safe utilization of fire extinguishing gas. Because of the way that the system adopts selective valves to guide the fm200 gas into the room on fire, a smarter way to avoid an accident is to monitor each room's situation. Lastly, It is worthy to mention that the combined rooms should be less than 8 including 8 in accordance with our standard.


Composition

The single zone pipe network fm200 fire suppression system consists of:

  • Fm200 cylinder
  • Container valve
  • Flexible hose
  • Liquid flow check valve
  • Gas control pipe
  • Gas flow check valve
  • Manifold
  • Pressure switch
  • Safety valve
  • Nitrogen pressure driving device
  • Flange

Auto Or Mechanical Mode FM200 Gas Suppression System Pipe Network Type Single Zone

Send your message to this supplier
Send Now

Auto Or Mechanical Mode FM200 Gas Suppression System Pipe Network Type Single Zone

Ask Latest Price
Watch Video
Brand Name :
xingjin
Certification :
CAL,CMA,CNAS,ILAC-MRA,CCC
Place of Origin :
China
MOQ :
2 set system
Price :
negotiation
Payment Terms :
T/T, L/C
Contact Supplier
video
Auto Or Mechanical Mode FM200 Gas Suppression System Pipe Network Type Single Zone
Auto Or Mechanical Mode FM200 Gas Suppression System Pipe Network Type Single Zone
Auto Or Mechanical Mode FM200 Gas Suppression System Pipe Network Type Single Zone
Auto Or Mechanical Mode FM200 Gas Suppression System Pipe Network Type Single Zone

Guangzhou Xingjin Fire Equipment Co.,Ltd.

Verified Supplier
10 Years
guangdong, guangzhou
Since 2010
Business Type :
Manufacturer, Exporter
Total Annual :
>50000
Employee Number :
>100
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement