Industrial Power Supply 250KW 300KVA 3 Phase Natural Gas Generator Set Prime Power 200KW
Gurantee
Within the guarantee period
Replace any part(s) for free which is found to be defective under normal use and service, in accordance with the maintenance schedule, and SevenPower pays for the transportation cost.
◆ HIGH ALTITUDE OPERATION
At high altitude, the standard gas mixer will be excessively rich. Performance will decrease, and fuel consumption will increase.
High altitude performance can be improved by installing a smaller diameter main fuel jet in the mixer and readjusting the pilot screw. If you always operate the engine at altitudes higher than 5000 feet (1500 meters) above sea level, have an authorized generator dealer perform this mixer modification.
Even with suitable mixer jetting, engine horsepower will decrease approximately 3.5% for each 1000 foot (300 meter) increase in altitude. The effect of altitude on horsepower will be greater than this if no carburetor modification is made.
Main Specifications
Model | SP250N | |
fuel | — | Natural Gas |
marks | — | Synchro Genset |
electrical output(KWe) | kVA/kWe | Continuous Power |
313/250 | ||
frequency | Hz | 50 |
voltage | V | 400/230 |
gas inlet pressure | kPa | 3-5 |
dimension (soundproof type) | mm*mm*mm | 3500*1800*2000 |
net weight | kg | 4000 |
NG consumption | m3/kW.h | 0.28 |
db(A)@7m | — | 59 |
Certificate | — | CE |
ignition system | — | Altronic |
speed governor | — | Woodward |
mixer | — | Venturi type |
gas filter | — | Madas |
zero regulator | — | Kromschroeder |
solenoid valve | — | Kromschroeder |
gas pressure gauge | — | Dungs |
Lambda auto control | — | Available on request with extral cost |
catalyst converter | — | Available on request with extral cost |
MCB | — | ABB |
GCB | — | ABB |
Controller | ComAp | |
Engine model | — | MAN MT13 |
Engine type | — | 6 cylinders,4stroke,water-coolled |
RPM | — | 1500 |
Compression Ratio | — | 11.5 |
Displacement | — | 12.419L |
Oil capacity | — | 40L |
Charging voltage | — | 24V(DC) |
Charging current | — | 5A(DC) |
Starting system | — | Electic-start |
Alternator model | — | Meccalte |
phase | — | 3 phase 4 wires |
insulation system | — | class H |
protection | — | IP23 |
Cooling Type | — | air cooled |
Optional Configurations