cabinet FM200(HFC-227ea) fire extinguishing device, also known as no pipe network FM200(HFC-227ea) fire extinguishing system, prefabricated FM200 fire extinguishing system, by fire extinguishing agent storage bottle, container valve, driver, high-pressure hose, pressure signal, nozzle, cabinet, etc., no need to install fire extinguishing agent pipeline, There is no need to set up a special bottle storage room. The device is set in the protection area, when the fire occurs, the fire extinguishing agent is sprayed directly to the protection area, the fire extinguishing agent has no pipeline loss, and the fire extinguishing speed is faster and the efficiency is higher. The device has three starting modes: automatic, manual and mechanical emergency operation.
Model
|
GQQ120/2.5-XL-40
|
Executive standards
|
GB16670-2006
|
Filling density
|
≤1120kg/M 3
|
Working temperature
|
0°C~50°C
|
Storage pressure
|
2.5MPa(+20°C)
|
Max working pressure
|
4.2MPa(+50°C)
|
System spray time
|
Computer room≤8s, others≤10s
|
Fire extinguishing design concentration
|
8-10%
|
System startup mode
|
Automatic,Pneumatic manual,Mechanical emergency
|
Fire extinquishing mothods
|
Fully submerged fire extinguishing
|
Cabinet FM200(HFC-227ea) fire extinguishing system Application:
The device is mainly applicable to the following fires:
1) Solid surface fire;
2) Liquid fire;
3) Gas fire that can cut off the gas source before extinguishing;
4) Electrical fire;
FM200 (HFC-227ea) Fire Extinguishing Agent Description:
FM200 (HFC-227ea) is used as fire extinguishing agent in the cabinet HFC-227EA fire extinguishing device. Sevofluoropropane is mainly used for chemical fire suppression and has the function of physical fire suppression. It is colorless, tasteless, clean, non-conductive, and does not pollute the protected object. It will not cause damage to property and precision facilities, and has no damaging effect on the atmospheric ozone layer (ODP value is zero). The extinguishing concentration is lower than the non-toxic reaction concentration (NOAEL concentration) of the human body, which is safe for the human body and is an excellent clean gas fire extinguishing agent.
Cabinet FM200 fire extinguishing system Safety warning:
1) When the FM200 is discharged, condensing steam fog will be generated, and the fire extinguishing speed is very fast by interrupting the combustion chain. If it is used in a place where people are working, the device is required to delay, and the personnel will be withdrawn within the delay time;
2) The user unit shall set up obvious warning signs in the following parts, and the wording of the signs is suggested as follows
3) Sign in the protected area: Warning! Hear the scene alarm, personnel should evacuate immediately
4) At the location of the emergency start button: Warning! Mechanical emergency start should confirm that no one in the protection area.