China make LHSR Model Pressure Reducing Regulator Use For Gas Fired Burner
Type HSR direct-operated, spring-loaded pressure reducing regulators provide control in residential, commercial,
and industrial applications for natural, manufactured, or liquefied petroleum gases.Internal relief across the diaphragm
helps minimize overpressure. Any outlet pressure over the start-to-discharge point of the nonadjustable relief valve
spring moves the diaphragm off the relief valve seat, allowing excess pressure to vent.Regulators meet ANSI B109.4/CGA 6.18.
Features
Globe Bodies
High Capacity
Compact Design
High Capacity Internal Relief
Meets or Exceeds ANSI B109.4 / CGA 6.18 Requirements
Fixed Factor / PFM Accuracy
Body Size and End Connection Styles
1inch NPT Globe Body
Allowable Inlet Pressure
Emergency: 150 psig / 10,3 bar
Maximum Operating Pressure: 125 psig / 8,6 bar
Allowable Outlet Pressure
Emergency (Casing): 25 psig / 1,7 bar
Maximum Operating Pressure to Avoid Internal Parts Damage: 3 psi / 0,21 bar differential above outlet pressure setting
Outlet Pressure
1.25 to 2.2psi/0.09 to 0.15bar
Outlet Pressure Ranges Of fisher HSR pressure regulator
4 to 6-inches w.c. (10 to 15 mbar)
6 to 8-inches w.c. (15 to 20 mbar)
8 to 10-inches w.c. (20 to 25 mbar
10 to 12.5-inches w.c. (25 to 31mbar)
12.5 to 20-inches w.c. (31to 50 mbar)
20 to 35-inches w.c. (50 to 87 mbar)
1.25 to 2.2 psig (0.09 to 0.15 bar)
Pressure Registration
Internal
Temperature Capabilities
-20 to 160°F / -29 to 71°C
Table 1. Maximum Operating Inlet Pressure
ORIFICE SIZE | WIDE-OPEN Cg | MAXIMUM OPERATING INLET PRESSURE TO OBTAIN | |||||
GOOD REGULATING PERFORMANCE | |||||||
Inch | mm | FOR RELIEF SIZING | psig | bar | |||
1/8 | 3.2 | 12.5 | 125 | 8.6 | |||
3/16 | 4.8 | 28.2 | 100 | 6.9 | |||
1/4 | 6.4 | 50 | 60 | 4.1 | |||
3/8 | 9.5 | 105 | 30 | 2.1 | |||
1/2 | 13 | 185 | 20 | 1.4 |