1, Model:CCEC Cummins NTA855-G2 A, 4-cycle
2, Standby Power:300KW / 375KVA 50HZ
3, Prime Power: 275KW / 344KVA 50HZ
3, Air Intake System:Turbo, Water/Air cooling
4, Fuel System: PT type fuel pump, EFC
5, Cylinder Arrangement:6 in line
6, Rated RPM:1500rpm
7, Governor Type:Electronic
8, Protection Grade:IP23
9, Connecting Type:3 Phase and 4 Wires, “Y” type connecting
Self - Exciting Cummins Diesel Generators , 6 Cylinder
Standby Power(50Hz) |
300KW / 375KVA |
Prime Power(50Hz) |
275KW / 344KVA |
Dimension & Weight
Standard Configuration (Open Type) |
Overall Size: 3030(mm)×1100(mm)×1850(mm) |
Weight: 2850kg |
General Features: |
Engine (CCEC Cummins NTA855-G2A) |
Radiator 40OC max, fans are driven by belt, with safety guard |
24V charge alternator |
Alternator: single bearing alternator IP23, insulation class H/H |
Absorber |
Dry type air filter, double fuel filter, oil filter, coolant filter |
Main line circuit breaker |
Standard control panel |
Two12V batteries, rack and cable |
Ripple flex exhaust pipe, exhaust siphon, flange, muffler |
User manual |
Engine Data
Manufacturer / Model: |
CCEC Cummins NTA855-G2 A, 4-cycle |
Air Intake System: |
Turbo, Water/Air cooling |
Fuel System: |
PT type fuel pump, EFC |
Cylinder Arrangement: |
6 in line |
Displacement: |
14L |
Bore and Stroke: |
140*152(mm) |
Compression Ratio: |
14.0:1 |
Rated RPM: |
1500rpm |
Max. Standby Power at Rated RPM: |
343KW/466HP |
Governor Type: |
Electronic |
Exhaust System |
|
Exhaust Gas Flow: |
1126L/s |
Exhaust Temperature: |
558℃ |
Max Back Pressure: |
10kPa |
Air Intake System |
|
Max Intake Restriction: |
10kPa |
Consumption: |
425L/s |
Air Flow: |
8180L/s |
Fuel System |
|
100%( Prime Power) Load: |
192.6 g/Kw.h |
75%(Prime Power) Load: |
196.1 g/Kw.h |
50%(Prime Power) Load:: |
208.4 g/Kw.h |
100%( Prime Power) Load: |
66.7L/h |
Oil System |
|
Total Oil Capacity |
38.6L |
Oil Consumption: |
≤0.24L/h |
Engine Oil Tank Capacity: |
36L |
Oil Pressure at Rated RPM: |
241-345kPa |
Cooling System |
|
Total Coolant Capacity: |
85L |
Thermostat: |
82-93℃ |
Max Water Temperature: |
104℃ |
Alternator SpecifiCAT-parts-partsion
GENERAL DATA
Compliance with GB755, BS5000, VDE0530, NEMAMG1-22, IED34-1, CSA22.2 and AS1359 standards.
Alternator Data
Number of Phase: |
3 |
Connecting Type: |
3 Phase and 4 Wires, “Y” type connecting |
Number of Bearing: |
1 |
Power Factor: |
0.8 |
Protection Grade: |
IP23 |
Altitude: |
≤1000m |
Exciter Type: |
Brushless, self-exciting |
Insulation Class, Temperature Rise: |
H/H |
Telephone Influence Factor (TIF): |
<50 |
THF: |
<2% |
Voltage Regulation, Steady State: |
≤±1% |
Alternator Capacity: |
350KVA |
Alternator Efficiencies: |
93.5% |
Air Cooling Flow: |
0.8m3/s |
Generating set data:
Voltage Regulation: |
≥±5% |
Voltage Regulation, Stead State: |
≤±1% |
Sudden Voltage Warp (100% Sudden Reduce): |
≤+25% |
Sudden Voltage Warp (Sudden Increase): |
≤-20% |
Voltage Stable Time (100% Sudden Reduce): |
≤6S |
Voltage Stable Time (Sudden Increase) |
≤6S |
Frequency Regulation, Stead State: |
≤5% |
Frequency Waving: |
≤0.5% |
Sudden Frequency Warp (100% Sudden Reduce): |
≤+12% |
Sudden Frequency Warp (Sudden Increase): |
≤-10% |
Frequency Recovery Time (100% Sudden Reduce): |
≤5S |
Frequency Recovery Time (Sudden Increase): |
≤5S |
Options
Competitive Advantage:
High Performance of loading Easy start
Nice protection User-friendly operation
Low running cost Environmental Long service life