Comap Generator Fittings Automatic Start Stop Controller Model CKG155
product presentation:
Generator Set Start & Protect: Used to start and protect a single generator set, realize the manual and remote start and stop of the generator set, data measurement, alarm indiCAT-parts-partsion, shutdown protection, etc.
LED Digital Tube Display: Light touch button operation to achieve precise measurement of various parameters, all configuration parameters can be adjusted from the front panel of the controller
Reliable Operation Easy Installation: The gasoline generator set controller has the advantages of simple operation, reliable operation, compact structure, and convenient installation
For Diesel & Gasoline Generator: The auto start stop control module can be widely applicable to data display and fault protection of various small diesel and gasoline generator sets
Embedded Installation Method: Modular structure design, flame retardant ABS plastic shell, embedded installation method, small size and easy installation
ifiCAT-parts-partsion:
Item Type: Generator Set Controller
Material: ABS
Working Voltage: DC9.0V to 18.0V continuous power supply - suitable for DC12V system
Whole Machine Power Consumption: Normal operation <1W, standby state <0.4W
Alternator Voltage Input:
Three-phase four-wire AC30V- AC360V (ph-N)
Three-phase three-wire AC50V- AC620V (ph-ph)
Two-phase three-wire AC30V- AC360V (ph-N)
Single-phase two-wire AC30V- AC360V (ph-N)
Alternator Frequency: 50Hz/60Hz
Package List:
1 x Generator Set Controller
2 x Bracket
1 x Wiring Frame
1 x Manual
Remote start sequence:
1. When the remote power‑on signal input is valid, enter the power‑on delay.
2. After the power‑on delay is over, the preheating relay output (if configured) enters the preheating delay.
3. After the preheating delay is over, the fuel relay outputs for 1s (if configured as fuel output), then the start relay output and the preheat relay are disconnected; if the genset does not start successfully within the starting time, the fuel relay and start relay stop output , Enter the start interval time, and wait for the another start (after the start interval time delay starts 3s, the preheating and energized shutdown will start output, after the start interval, the energized shutdown output will be disconnected, and the fuel output will be preheated after 1s. The output is disconnected).
4. Within the set number of starts, if the genset fails to start successfully, the start failure alarm indiCAT-parts-partsor will light up.
5. At any start, if the start is successful, it will enter the safe running time. During this time, the low oil pressure input and the under‑pressure alarm are invalid. After the safe running delay is over, it will enter the start‑up idle delay (if the start‑up is idle The delay is configured).
FQA:
Q1: Who are you?
A1: We are factory and exporter of generator parts since 2006.
Q2: How to place order?
A2: Send order link or contract ----- You confirm and pay -----Arrange shippment ----Upload the tracking number---- You received.
Q3: What is the warranty?
A3: Warranty is 1 years. During the warranty, no mater our quality problem or your wrong process cause broken, we will send new and free one to replace.
Q4: Do you check all your goods before delivery?
A4: Yes, we will check the quality 100% before we send out the goods.
Q5: How long is delivery time?
A5: If goods in stock,it needs 2-3 days after payment. If big quality and not in stock, it will needs about 3-7 days to make.
Q6:What is your payment way?
A6 : T/T, Western Union, Paypal, Money Gram, RMB directly. Cash.
Q7: What is your shipping way?
A7: If by our forwarder, we will send it by Express, like FedEx,DHL,UPS,TNT,Aramex Etc.
If you have your own forwarder in China, it is free shipping to your forwarder's warehouse.
Q8: What is your packing type?
A8: All of our goods are packed by plastic bag to waterproof and protect the goods during the delivery.