TBC-DS5 Closed Loop Hall Effect Current Sensor 6A to 50A Rated input
TBC-DS5 series multi-range current sensor is a closed loop device based on the measuring principle of the hall effect and null balance method, with a galvanic isolation between primary and secondary circuit. It provides accurate electronic measurement of DC, AC or pulsed currents.
Electrical data(Ta=25℃±5℃) |
Type Parameter | TBC06DS5 | TBC15DS5 | TBC25DS5 | TBC50DS5 | |
Rated input (Ipn) | 6 | 15 | 25 | 50 | A |
Measure range(Ip) | 19.2 | 48 | 80 | 150 | A |
Secondary turns(Ns) | 960±1 | 1200±1 | 1000±1 | 1000±1 | T |
Internal resister | 100±0.1% | 50±0.1% | 25±0.1% | 12.5±0.1% | Ω |
Rated output (Ip=±Ipn) | ±0.625±0.5% | ±0.625±0.5% | ±0.625±0.5% | ±0.625±0.5% | V |
Supply voltage | +5±5% | V | |||
Power consumption | ≤20+Ip/Ns | mA | |||
Zero voltage | @ Ip=0 2.5±0.5% | V | |||
Zero voltage drift | @ -40~+85℃ ≤±0.5 | mV/℃ | |||
Linearity | @ Ip=0-±Ipn ≤0.1 | %FS | |||
Total precision | ≤±0.7 | % | |||
di/dt accurately followed | >50 | A/µS | |||
Response time | @ Ip=Ipn, 50 A/µS ,10%-90% <500 | nS | |||
Bandwidth | @ -1db DC~200 | KHZ | |||
Galvanic isolation | @ 50HZ,AC,1min 2.5 | KV |
Applications |
AC variable speed drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies(SMPS)
Power supplies for welding applications
Mechanical dimension(for reference only) |
Remarks:
1. All dimensions are in mm.
2. General tolerance ±1mm.
Pin connections |
Turns | IPN(A) | Vout(V) Rated output voltage | [mΩ] | [uH] | Connect point |
1 | ±6(±15, ±25,±50) | 2.5±0.625 | 0.18 | 0.013 | ![]() |
2 | ±3(±7.5, ±12.5,±25) | 2.5±0.625 | 0.81 | 0.05 | ![]() |
3 | ±2(±5, ±8.3,±16.6) | 2.5±0.625 | 1.62 | 0.12 | ![]() |
Directions for use |
When the current will be measured goes through a sensor, the voltage will be measured at the output end.
(Note: The false wiring may result in the damage of the sensor)
Custom design in the different rated input current and the output voltage are available.
Standards |
General date |
Value | Unit | Symbol | |
Operating temperature | -40 to +85 | ºC | TA |
Storage temperature | -40 to +125 | ºC | TS |
Mass(approx) | 10 | g | M |
Characteristics chart |
Pulse current signal response characteristic Effects of impulse noise