HVAC System Motorized General Damper Actuator 10Nm 2-point and 3-point
Damper actuators for operating air control dampers in ventilation and air-conditioning systems for building services installations.
10 Nm, 150 s, 95°
AC 230 V, Open/Close, 3-point, 1 x SPDT
IP 54, Manual override with push-button
Control with single- / 2-wire contact
Auxiliary switch integral, potential-free, 0...100 % adjustable
Connection PVC cable 1m
Direction of rotation reversible (right/left)
Angle of rotation limit. mechanical integral
Spindle driver universal spindle clamp
Rating 1 mA...3(0.5)A, AC 250 V
Electrical data
Nominal voltage AC 24V, 50/60Hz, DC 24V
Nominal voltage range AC/DC 19.2 …28.8V
Power consumption In operation 1 W @ nominal torque
At rest 0.2W
Auxiliary switch 1×SPDT, 1mA…3(0.5)A, AC250V
(0…100% adjustable)
Connection Motor Cable 1m, 3×0.75mm2
Auxiliary switch Cable 1m, 3×0.75mm2
Functional data
Torque (nominal torque) Min.10Nm @ nominal voltage
Direction of rotation Reversible with switch
Manual override Gearing latch disengaged with pushbutton, self-resetting
Angle of rotation Max.95°, limited on both sides by means of adjustable,mechanical end stops
Running time 150 s
Sound power level Max.35Db (A)
Position indication Mechanical, pluggable
Safety
Protection class Ⅲ Safety extra-low voltage
Degree of protection IP54 in any mounting position
EMC CE according to 89/336/EEC
Mode of operation Type 1(to EN60730-1)
Ambient temperature range -30…+50℃
Non-operating temperature -40…+80℃
Ambient humidity range 95% r.H., non-condensating(EN 60730-1)
Maintenance Maintenance-free
Weight Approx.750g
Dimension
Writing Diagram