ISO Class 7 Dust Free Modular Prefab Clean Room
With an increasing emphasis on maximizing product yield, improving quality control and ensuring safety, companies throughout many industries are looking to install cleanrooms or controlled environments in their facilities. No longer are cleanrooms limited to high tech semiconductor manufacturing or university research labs. Today, cleanrooms are being used in all types of environments.
Main Features
(1) Assembly structure designed, easy installation and easily moved
(2) Directional wheels can be installed, suitable for small building and high cleanliness area;
(3) Modular design: clean booth can be as small as several square meters and can be as large as hundreds of square meters
(4) It has large useful and effective area; while compared with traditional clean room, it has such features like low investment, high return and stable.
| |
| | | |
| | | | |
| | Cold rolled steel /Aluminum/Stainless steel/sandwich panel |
| Plexiglass,Soft curtain,Anti-static strip curtain/sandwich panel |
| | | | |
| | | | | |
| | | | |
| | | | |
| | |
| | | | | |
| | | | |
Architectural Finishes
- Low wall air returns.
- Wall systems: modular purpose-built wall systems depending on the application of the cleanroom. Biotech applications require non-shedding systems, with monolithic seams and coving to remove 90° angles, allowing wet washed down or VHP fogging to achieve sterile requirements. Nanotechnology and other non-sterile cleanroom types utilize non-shedding systems and are regularly dry wiped or vacuumed.
- Ceiling systems: purpose-built ceiling systems are utilized for ISO 7 conditions depending on the application of the cleanroom. Biotech and pharmaceutical applications require walkable or panelized ceiling systems to promote monolithic washable surfaces, and access to maintain lights and filter media from the top side of the ceiling without breaching the certified and validated space. Nanotechnology and other non-sterile applications commonly utilize gasketed grid systems with non-shedding blank ceiling tiles where devices such as filtration or lights are not populated.
- Flooring systems most commonly a resinous floor system, or heat sealed vinyl flooring system, with specific attributes depending on the application (i.e. chemical resistance, coving, static control, rolling weight loading / impact resistance, non-slip).
- Miscellaneous architectural features to include types of doors, viewing windows, glass walls, pass-thrus, sprinkler heads / fire suppression, Wi-Fi / network access, security cameras, and access control devices.
Recommended Gowning & Housekeeping
- Recommended gowning requirements: head cover, goggles, beard cover, lab coat, foot coverings or booties, and gloves suitable to the task (i.e. vinyl, latex, nitrile)
- Gowning room: separate (typically a lesser pressure, and one classification less stringent; i.e. ISO 8 airlock) prior to entering the ISO 7 Cleanroom
- No particle generation materials are allowed past material or personnel airlocks such as carboard, pallets, paper, dry erase boards, etc.