HEPA/ULPA/PTFE Fan Filter Units FFU With H13 H14 U15 HEPA Filter
The Fan filter Unit ffu consists essentialy of the housing, a compact fanunit with inlet-nozzle, motor and the HEPA filter cell with filter frame. Special deflectors avoid a bypass flow of the supply air directly into the return-air. The sound absorber reduces fan noise.
Technical Data:
Model | AL-FFU2*4 |
Size(W*L*H)mm | 1175*575*350mm |
Weight | 30KGS |
Frequency | 50 Hz / 60 Hz (110V/120V /220V/230V/240V) |
Rated current | between 1.8 A and 1.6 A |
Rated capacity | 370w |
Number of revolutions min.: | 300 1/min | max.: 1,304 1/min |
Flow velocity | 0.45 m/s adjustable |
External pressure differ | 40PA |
Air volume flow | 2,333 m³/h |
Power consumption | 150W |
Sound power level pressure side: | 63 dB (A) |
Clean room sound pressure level | 50 % occupancy: 66 dB (A) |
The following additional components at the air-inlet side are available:
Prefilter for coarse particle separation
AMC-Filter for the filtration of gaseous contaminations
Return-air covers for prefilter and AMC filter
Cover return-air duct
If necessary filter cell class H13 to U17 can be used.
The FFU-motors have sufficient reserve capacity to overcome additional system pressure loss due to, e.g. raised floor, return-air ducts, prefilter or AMC filter. The FFU-RA-AC is driven by a special developed single-phase external rotor-motor with internally wired thermal contacts for overload protection. The FFU-RA-EC operates with a electronic commutated external rotor motor.
FFU Accessories:
Particle Filter (All Filters as Filter with dry sealant. Filters with fluid sealant are available upon request.)
AMC Filter for filtration of gaseous contaminants
Prefilter for coarse particle filtration (Prefilter incl. Filterframing made in Aluminium)
Particle Filter-installation frame
Aerosolinlet-/Measurementconnector
Properties about FAN FILTER UNIT:
Easy device installation from below (cleanroom side) with bearing rails
Optional installation from top (plenum side)
Best price-performance ratio
With connection for particle and differential pressure measurement
FFU sizes fit in ceiling grid size (1200 mm × 1200 mm, 1200 mm × 900 mm, 1200 mm × 600 mm)
Applicable for larger cleanroom areas
Aluminium housing (standard)
HEPA / ULPA filter classes H13 to U17
Installed radial fan balancing grade G= 2,5 according to DIN ISO 1940-1, motor with internal wired thermal contact