Specifications
Brand Name :
GDZX
Model Number :
ZXBXZ
Certification :
ISO9001
Place of Origin :
China
MOQ :
1Set
Payment Terms :
L/C, T/T, Western Union, MoneyGram,
Supply Ability :
1200Sets/ year
Delivery Time :
7-20 work days
Packaging Details :
Carton or Wooden Case
Rated output voltage :
0 - 1000kV
output frequency :
30 ~ 300Hz
Duty Cycle :
Continuous working time 60mins one time at full power output.
Quality factor :
30-90
Frequency adjustment sensitivity :
0.1Hz
instability :
<0.05%.
Power Supply :
380/220V±15%, 50Hz ± 5%.
Description
High Voltage Resonant Test System
500KV 50HZ AC High Voltage Resonant Test System For Substation
This series devices are designed for AC withstand voltage test of substation primary equipment under 550KV or below, mainly composed of variable-frequency power supply, exciting transformer, reactor and capacitive Voltage divider.


Features

1. Easy to operate, two working modes: manual and automatic.

2. Can set Test Voltage, frequency range, protective current and operating time.

3. Smaller size, lighter weight compared with same voltage level same capacity reactor.

4. Small temperature rise at rated load. Strong protection, good stability. Multiple functions, cost effective.

5. Dry type epoxy cast, high mechanical strength, good insulation, nice and reliable.

6. Adjustable capacity of frequency control source.

7. With 220V or 380V single phase power, convenient for on-site power sourcing.

8. Flexible configuration. Different type reactors for option to meet different test object requirements.



Technical Indicators

1. Rated output voltage: 0 - 1000kV, output frequency: 30 ~ 300Hz.Waveform: pure sine wave, THD <1.0%.

2. Duty Cycle: Continuous working time 60mins one time at full power output.

3. Quality factor: 30-90. Frequency adjustment sensitivity: 0.1Hz, instability <0.05%.

4. Power Supply: 380/220V±15%, 50Hz ± 5%.

Rated output voltage 0 - 1000kV
output frequency 30 ~ 300Hz
Waveform pure sine wave
THD <1.0%.
Duty Cycle Continuous working time 60mins one time at full power output
Quality factor 30-90
Frequency adjustment sensitivity 0.1Hz, instability <0.05%.
Power Supply 380/220V±15%,
Power frequency 50Hz ± 5%.

500KV 50HZ AC High Voltage Resonant Test System For Substation

Reference Pictures

Send your message to this supplier
Send Now

500KV 50HZ AC High Voltage Resonant Test System For Substation

Ask Latest Price
Brand Name :
GDZX
Model Number :
ZXBXZ
Certification :
ISO9001
Place of Origin :
China
MOQ :
1Set
Payment Terms :
L/C, T/T, Western Union, MoneyGram,
Contact Supplier
500KV 50HZ AC High Voltage Resonant Test System For Substation
500KV 50HZ AC High Voltage Resonant Test System For Substation
500KV 50HZ AC High Voltage Resonant Test System For Substation
500KV 50HZ AC High Voltage Resonant Test System For Substation

Wuhan GDZX Power Equipment Co., Ltd

Verified Supplier
8 Years
hubei, wuhan
Since 2012
Business Type :
Manufacturer, Exporter
Total Annual :
8 million-10 million
Employee Number :
100~120
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement