Factory directly WDR Series Industrial Electric Steam Heating Boiler with A-class
Features of electric heating steam boiler
1. with no pollution, low noise, high thermal efficiency, simple operation, simple installation, compact structure and other characteristics.
2. The electric heating boiler, furnace body and control system manufactured by the company adopt the split-type structure, which can effectively avoid the leakage of electricity and other safety problems caused by temperature rise.
3. electric heating boiler internal heating components are independently set, each group of components are connected by centralized beam flange, with high mechanical strength, easy maintenance, long service life and other characteristics.
4. The capacity of the boiler ranges from 0.3 to 4T/h, and the power ranges from 0.24MW to 2.8MW.
5. electric heating boiler can be used in hotels, schools, residential heating, chemical industry, smelting, building materials and other industries and occasions.
6. Using high quality electric heating pipe, the surface load is very low, so that the heating process is more stable and safe, the service life of the equipment is longer.
Advantages
1. An Electric Heating Steam Boiler is a pressure vessel device that converts electrical into heat and then heat the water to produce steam.
2. The piezoelectric furnace with a water storage capacity of 30L or more at the highest safe water level is an electric heating boiler;
3. The Electric Heating Steam Boiler adopts Japan Fuji temperature control instrument, using PID self-tuning intelligent temperature control technology, the control precision can reach the temperature of about ±1 °C, and accurately control the temperature range used;
4. The heating main power supply uses solid-state module non-contact switch circuit, adapt to frequent switching, and no interference to the power supply network. And has anti-dry burning.
5. Electric Heating Steam Boiler Can be designed according to user requirements to add hot oil cooling system to meet the production process requirements of rapid cooling after heating;
6. To achieve centralized control of the boiler.
According to this automated system, the automatic timing switching of the boiler in the boiler room is realized, thereby realizing the circulating operation of the gas boiler, which not only can realize the energy saving of the boiler heating, but also can effectively extend the service life of the boiler.
Electric Heating Steam Boiler data sheet as follow (for reference only) :
WDR Series Electric Heating Steam Boiler - Technical Parameter | ||||||||
Model | WDR0.75-1.0 | WDR1-1.0 | WDR1.5-1.0 | WDR2-1.0 | WDR3-1.0 | WDR4-1.25 | ||
Project | unit | |||||||
Rated evaporation | t/h | 0.75 | 1 | 1.5 | 2 | 3 | 4 | |
Fixed work stress | MPa | 1 | 1 | 1 | 1 | 1 | 1.25 | |
Saturated vapor temperature | °C | 184 | 184 | 184 | 184 | 184 | 193 | |
input power | KW | 540 | 720 | 1080 | 1440 | 2160 | 2880 | |
Input Current | A | 810 | 1080 | 1620 | 2160 | 3240 | 4320 | |
Rated voltage | V | 380 | ||||||
Power × number of groups | KW×P | 36×15 | 36×20 | 36×30 | 36×40 | 36×60 | 36×80 | |
a main steam valve caliber | DN | 40 | 40 | 65 | 65 | 80 | 100 | |
b safety valve caliber | DN | 2×40 | 2×40 | 2×40 | 2×40 | 2×40 | 2×40 | |
c inlet diameter | DN | 40 | 40 | 40 | 40 | 40 | 40 | |
d drain valve caliber | DN | 40 | 40 | 40 | 40 | 40 | 40 | |
Boiler dimensions | L | Mm | 2800 | 2950 | 3450 | 3500 | 3950 | 4100 |
L1 | Mm | 2400 | 2500 | 3050 | 2880 | 3200 | 3550 | |
W | Mm | 1800 | 1900 | 2180 | 2000 | 2100 | 2480 | |
W1 | Mm | 1550 | 1600 | 1430 | 1880 | 1980 | 2120 | |
H | Mm | 1550 | 1600 | 2100 | 2500 | 2650 | 2980 | |
H1 | Mm | 1300 | 1350 | 1850 | 1900 | 2100 | 2200 | |
Control cabinet size | A long | Mm | 1200 | 1200 | 1500 | 1500 | 1800 | 2100 |
B wide | Mm | 500 | 600 | 600 | 600 | 600 | 600 | |
C high | Mm | 1800 | 800 | 2000 | 2000 | 2200 | 2200 | |
weight | Kg | 2300 | 2850 | 3220 | 3550 | 4100 | 5200 |
Electric Heating Steam Boiler in factory work shop :