Specifications
Brand Name :
OEM/HRD
Model Number :
PWM3360X,PWM3390X,PW33120X
Certification :
ISO9001,CE
Place of Origin :
CHINA
MOQ :
5
Price :
4500-8000USD
Supply Ability :
500PCS /WEEK
Packaging Details :
standard for export
Description

POWERWELL MAX series Online HF UPS 3:3phase 60-120kVA,1.0PF

(For 380/400/415Vac, Line-Line Voltage)

Introduction:Powerwell MAX series 3 phase 60-120kVA is transformer-less a high quality uninterruptible power supply, which has adopted the world leading electrical and electronic technology to increase performance and high reliability(MTBF>200,000h). Being kin to 1.0 input power factor and less than 3% THDi lead this UPS green and energy saving.

And similar modular design for convenient maintenance.

Perfect Applications:

Internet Servor, Medium-scale network system / computing center, bank and securities, business server group, precision equipment, etc.

Features: complete digital control technology

Fully digital control with DSP chip processor, all the subsystems are digital controlled including the IGBT rectifier, inverter, charger etc.

Excellent electrical properties

True online double conversion instruction offers the safe and effective power protection for various loads, with strong output load capacity;

High input power factor, green and energy-saving

Input PF above 0.99 and efficiency up to 96%;

Similar Modular design for Easy Maintenance

Dual AC input source supportable

Allowable AC and bypass 2 input ac source

Strong environmental adaptability

Wide input voltage and frequency range, adaptation to all kinds of climatic and geographical environment

Comprehensive protection measures

The adoption of advanced technology (IGBT driving technology, IGBT soft over-current shutdown) improves the reliability and safety of inverter

Intelligent battery management (ABM)

Adopting the intelligent battery management:

Intelligent charger:interval three-stage charging process( constant current,constant voltage, float charging and charger shut off, when battery voltage decrease to a lower level, charger restarts to work)

Battery temperature compensation

Online detecting battery status,

The max battery charging current can set by end users according to the battery features, to avoid any damage caused by the big charging current;

Periodic self-test battery, detecting the battery problems timely;

Cold start and AC start Function

Directly start the UPS through battery or start UPS through Mains only.

Superior network monitoring capabilities

Communication port (RS232, USB, and so on) connecting with computer,SNMP card optional,

Friendly interface LED with high resolution LCD

Parallel up to 8 units

Technical specification:

Model PWM3360X PWM3390X PWM33120X
Power Rating 60kVA 90kVA 120kVA
Main Input
Grid System 3 Phases + Neutral + Ground
Rated Input Voltage 380/400/415VAC (L-L)
Rated Frequency 50/60Hz
Input Voltage Range 304~478Vac (Line-Line),full load
228V~304Vac (Line-Line),load decrease linearly according to the min phase voltage
Input Frequency Range 40Hz~70Hz
Input PF >0.99
Input THDi <3% (full Linear Load)
Bypass Input
Rated Bypass Voltage 380/400/415VAC (Line-Line)
Rated Frequency 50/60Hz
Voltage Range Selectable, default -20%~+15%
Up limited: +10%, +15%, +20%, +25%
Down limited: -10%, -15%, -20%, -30%, -40%
Frequency Range Selectable, ±1Hz, ±3Hz, ±5Hz
Bypass Overload 125%, long time operation
125%< load <130%, last for more than 10 minutes
130%<load<150%,last for more than 1 minutes
>150%, last for more than 300ms
Output
Rated Inverter Voltage 380/400/415VAC (Line-Line)
Rated Frequency 50/60Hz
Output Power Factor 1.0
Voltage precision ±1%
Transient Response <5% for step load (20% - 80% -20%)
Transient recovery < 30ms for step load (0% - 100% -0%)
Output Voltage THDu <1% from 0% to 100% linear load
<5% full non-linear load according to IEC/EN62040-3
Overload Capacity
<110%, 60min;
110%~125%,10min;
125%~150%,1min;
>150%,200ms
Frequency Regulation 50/60Hz±0.01%
Synchronized Range Settable, ±0.5Hz ~ ±5Hz, default ±3Hz
Synchronized Slew Rate Settable, 0.5Hz/S ~ 3Hz/S, default 0.5Hz/S
Battery And Charger
Battery Rate Voltage ±240VDC
Charger Voltage precision 1%
Charger Power max=20% *Output power
Efficiency
Normal Operation >96%
Battery Operation >95%
System
Display LED + LCD + touch screen
Interface RS232, RS485, USB,Programmable dry contact
Option battery cold start,SNMP,AS400,parallel kit,Lightning protection components,Dust Filter,LBS
Environmental
Operation Temperature 0 ~ 40 ℃
Storage Temperature -40 ~ 70 ℃
Relative Humidity 0 ~ 95% Non condencing
Noise (1 meter) 65dB @ 100% load, 62dB @ 45% load
Altitude <1000m, Load derated 1% per 100m From 1000 ~ 2000m
Physical data
Cabinet Dimension(W*D*H,mm) 600*980*950 600*980*1400 600*980*1400
N.W (kg) 170 231 266

Note:Any specification subject to change without notice;

Send your message to this supplier
Send Now

PWM Series Online HF UPS 60-120kVA For Stable Energy Supply

Ask Latest Price
Brand Name :
OEM/HRD
Model Number :
PWM3360X,PWM3390X,PW33120X
Certification :
ISO9001,CE
Place of Origin :
CHINA
MOQ :
5
Price :
4500-8000USD
Contact Supplier
PWM Series Online HF UPS 60-120kVA For Stable Energy Supply

Shenzhen HRD SCI&TECH CO.,Ltd

Verified Supplier
17 Years
guangdong, shenzhen
Since 2010
Business Type :
Manufacturer, Exporter
Total Annual :
15,000,000-200,00,000
Employee Number :
300~500
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement