4AD module with 4 channels suitable for 0-10V and 4-20mA analogue inputs
4DA module with 4 channels suitable for 0-10V and 4-20mA analogue outputs
4AD-PT module with 4 channels suitable for PT100 temperature probes/ analogue inputs
4AD-TC module with 4 channels suitable for thermocouple temperature probes/ analogue inputs
Manufacturer's Part No. | Analogue Range | Compensation Temperature Range |
FX3U-4AD-ADP | 0 to 10Vdc, 4 to 20mA | 2.5mV/10μA |
FX3U-4DA-ADP | 0 to 10Vdc, 4 to 20mA | 2.5mV/10μA |
FX3U-4AD-PT-ADP | 0.1°C | -50 to 250°C |
FX3U-4AD-TC-ADP | 0.3°C (J type)/ 0.4°C (K type) | -100°C to 600°C (J type) -100°C to 1000°C (K type) |
These modules fit on the left-hand side of FX3U base units and require one of the following modules to connect to the PLC: FX3U-232-BD (539-0869), FX3U-422-BD (539-0875), FX3U-485-BD (539-0881), FX3U-USB-BD (539-0897), FX3U-CNV-BD (539-0904). Supply voltage is taken from PLC base unit.
FX3U CPU's are compatible with existing FX2N expansion modules as well as the new FX3U ADP expansion modules and may be used as a replacement for FX2N PLC's.
Manufacturer Series | MELSEC FX | |
Number of Outputs | 4 | |
Output Type | Analogue, Relay, Transistor | |
For Use With | MELSEC FX Series | |
Number of I/O | 4 | |
Voltage Category | 5 → 24 V dc | |
Length | 90mm | |
Width | 17.6mm | |
Depth | 89.5mm | |
Dimensions | 90 x 17.6 x 89.5 mm |
For more specifications
Name of product | Analog output | ||
---|---|---|---|
Form name | FX3U-4DA-ADP | ||
Standard fit | CE (EMC), UL/cUL, KC, ABS, DNV, LR, GL, BV, RINA, NK, KR | ||
Performance specifications | Analog output | Analog output range | Voltage output DC0V-10 V (external load 5 k Ω ~ 1 M Ω) Current output DC4mA ~ 20 mA (external load 500 Ω below) |
Number of output channels | 4-channel | ||
Output characteristics | Individually for each channel, you can set output mode (voltage / current output). | ||
Digital input | 12-bit binary | ||
Resolution | Voltage output 2.5 mV (10 V × 1 / 4000) Current output 4 μA (16mA×1 / 4000) | ||
Overall accuracy | Voltage output Ambient temperature 25 ° c ± 5 ° c: for full scale 10 V ± 0.5% (± 50 mV) Ambient temperature 0 ° c ~ 55 ° c: for full scale 10 V ± 1.0% (± 100 mV) External load resistance (Rs) 5 k under the Ω of the following calculations: increases. (Increases 1% per 100 mV) (47 × 100) ÷ (Rs+47)?0.9(%) Current output Ambient temperature 25 ° c ± 5 ° c: for full scale 16 mA ± 0.5% (± 80 μA) Ambient temperature 0 ° c ~ 55 ° c: for full scale 16 mA ± 1.0% (± 160 μA) | ||
D/a conversion time | FX3U/FX3UC sequencer 200 µ s (data updated every operation cycle) FX3G/FX3GC sequencer 250 μ s (data updated every operation cycle) | ||
Insulation scheme | -Analog output channels and between the sequencer is isolated by Photocoupler -Analog output, and power supply between the isolated DC/DC converter by ? Each channel between the non-insulated. | ||
The occupancy number | 0 points (unrelated to maximum input and output number of sequencer ) | ||
Apply sequencer | FX3G, FX3U, FX3GC, FX3UC (the FX3UC-32MT-LT Ver.1.20 or later) Connection to FX3G is a FX3G-CNV-ADP is required. FX3U and FX3UC-32MT-LT (-2) connecting the function expansion board is required. | ||
Mass | 0.1 kg | ||
General specifications | Ambient temperature | 0-55 ° c, and operating: -25 ~ 75 ° c, and save time | |
Relative humidity | ... Operating 5 ~ 95% RH (non-condensing): | ||
Vibration resistance | DIN rail mounting: | < Frequency: 10-57 Hz > piece amplitude: 0.035 mm X, Y, Z directions 10 times (total 80 minutes each) | |
DIN rail mounting: | < Frequency: 57-150 Hz > acceleration :4.9m/s2 X, Y, Z directions 10 times (total 80 minutes each) | ||
Direct mounting: | < Frequency: 10-57 Hz > piece amplitude :0.075mm X, Y, Z directions 10 times (total 80 minutes each) | ||
Direct mounting: | < Frequency: 57-150 Hz > acceleration :9.8m/s2 X, Y, Z directions 10 times (total 80 minutes each) | ||
Impact resistance | 147 m / s 2 the interaction time is X, Y, Z directions three times in 11 ms half-sine pulse | ||
Noise immunity | Noise voltage rise 1,000 VP-p, noise width 1 μs, a 1 ns, 30-100 Hz noise Simulator | ||
Withstand voltage | Bulk all Terminal and ground terminal while: AC 500v for 1 minute | ||
Insulation resistance | Bulk all Terminal and ground terminal between :DC500V Megger at Ω over 5 M. | ||
Grounding | D seeds ground (ground resistance: below 100 Ω) [common grounding and electrical system is unavailable] Grounding is only on the ground or common ground and see. | ||
Operating atmosphere | Not corrosive, flammable gas, conductive dust (dust) is not severe | ||
Use advanced | less than 2000 m Under the pressure exceeding atmospheric pressure environment cannot be used. You may fail. | ||
Power supply specifications | Power supply | DC5V15mA (internal power supply from the sequencer) DC24V+20%-15% 150ma (external power supply) |