Production Description:
Fan Filter Unit (FFU) is a of type of motorized air filtering equipment. It is used to supply purified air to clean-rooms, laboratories, medical facilities or micro environments by removing harmful airborne particles from recirculating air. The units are installed within the system's ceiling or floor grid. Large clean-rooms require a proportionally large number of FFUs, which in some cases may range from several hundred to several thousand. Units often contain their own pre-filter, HEPA filter and internally controllable fan air distribution.
Specification:
1.Dimension: 570*570*340mm
2.Air Filter Size: 570*570*69
3.Air Volume: 700-1800 m³/h
4.External Static Pressure: 98Pa
5.Power Supply Standard: 220V
6.Filter Efficiency:≥99.9995% @≥0.3μm
7.Shock: ≤0.4m/s2
8.Noise:≤55Db(a)
9.Main body material: stainless steel, aluminum alloy, galvanized plate
Model Parameters | TR-FFU-F1 | TR-FFU-F2 | TR-FFU-F3 | TR-FFU-F4 | |||
TR-FFU-F1X | TR-FFU-F2X | TR-FFU-F3X | TR-FFU-F4X | ||||
Nominal volume (m³/h) | 2000 | 1800 | 1000 | 900 | |||
NoiseDb(A) | 54~60 | ||||||
Hepa filter efficiency | ≥99.99% ~ 99.9995%( @≥0.3μm) | ||||||
Power | AC220V±10%,1φ,50HZ±2HZ | ||||||
The input power (W) | 180 | 180 | 145 | 75 | |||
Envelop dimensions (mm)L*W*H | 1220*610*390 | 1170*570*340 | 610*610*390 | 570*570*340 | |||
Hepa filter specifications (mm) | 1220*610*69 | 1170*570*69 | 610*610*69 | 570*570*69 | |||
Coarse efficiency filters specifications (mm) | 495*495*21 | 495*495*21 | 395*395*21 | 395*395*21 |