1. Design condition of open type cooling tower:
Inlet temperature 37°C, outlet 32°C; temperature difference 5°C;
Wet bulb temperature 27°C, and atmospheric pressure 99400Pa.
Specifications and dimensions are subject to change without notice.
2. Main features for open type cooling tower:
1. Suspension structure: stainless steel structure, painted with epoxy-(coal)tar or Chlorosulfonated polyethylene after plated with zinc
2. Enclosure structure: polyester glass steel, with light weight, high strength corrosion resistant, anti aging, long service life
3. Air duct: Kinetic energy recovery type, reasonable air distribution with high efficiency
4. Fan: aerofoil epoxy-(coal)tar blade, features big air flow, high efficiency, low noise and corrosion resistance
3. Technical Parameter of Open Type Cooling Tower :
Model | Flow | Motor Power | Dimension of Fan | Air Flow | Water Pressure | Weight | |
Net | Gross | ||||||
LSK-10 | 10m3/h | 0.37kw | 600mm | 140cmm | 13KPa | 54kg | 290kg |
LSK-20 | 20m3/h | 0.75kw | 730mm | 200cmm | 16KPa | 98kg | 500kg |
LSK-60 | 60m3/h | 1.5kw | 1150mm | 450cmm | 18KPa | 260kg | 1280kg |
LSK-125 | 125m3/h | 2.2kw | 1410mm | 950cmm | 23KPa | 580kg | 1680kg |
LSK-200 | 200m3/h | 4kw | 1800mm | 1500cmm | 33KPa | 1050kg | 2770kg |
LSK-300 | 300m3/h | 7.5kw | 2400mm | 2200cmm | 34KPa | 1800kg | 3790kg |
LSK-500 | 500m3/h | 15kw | 3400mm | 3750cmm | 42KPa | 3950kg | 9350kg |
LSK-800 | 800m3/h | 22kw | 3700mm | 5400cmm | 45KPa | 4900kg | 12100kg |
LSK-1000 | 1000m3/h | 30kw | 4200mm | 7200cmm | 47KPa | 5800kg | 13400kg |
4. Brief Introduction Of Open Type Cooling Tower:
Water Cooling Tower for Industrial Refrigeration
1, The strength of the cooling tower shell adopts the high quality glass fiber production, acid and alkali resistant, anti-aging, and beautiful, is like new after long-term used.
2, The cooling tower body metal structure are processed by hot dip galvanized, greatly reduce oxidation, more durable, prolong life.
3, The cooling tower heat dissipation material made of high quality PVC film film curvy corrugated design, effectively extend the period of high temperature water and air heat exchanger, uniform water distribution, water, greatly improving in thermal efficiency, drift to minimize water, save energy consumption.
4, The cooling tower cooling fan blade forward type space warps, phoenix high volume, low noise, low energy consumption.
5. The cooling tower cooling motor adopts closed waterproof, smooth operation, long service life.
5. Application of Open Cooling Tower:
1. Cooling tower is mainly used for cooling in air conditioning system, frozen series, injection molding, leather, foam, power generation, steam turbine, aluminum processing, air compressors, industrial cooling water and other fields;
2. Most used for air conditioning cooling, freezing, plastic chemical industry;
3. Closed circuit cooling tower have the Attractive shape: the Small dimension of shape, the low height of the tower, light weight of tower, and multiform layout in covering the area.
6.Advantage of open type cooling tower:
1. Motor : selection of the world famous brand Siemens closed ultralow noise motor , the motor insulation class F , protection class IP55, high efficiency , long life , high temperature , strong ability to adapt to changes in voltage , can fully guarantee the cooling tower life and operating results.
2. fans : selection of test flying Industrial R & D chord solitary large , low-speed , high winds , high-strength aluminum alloy silent type blower is 6 to7 times more common aluminum alloy sheet , maintaining good precision performance ; also has light weight, high efficiency , energy , balancing good , vibration, security and stability, long life and other advantages.
3. Transmission: The choice of NSK or NTN bearings standard bearing , long life, easy to damage ; belt use Japanese Samsung waterproof slip -belt , high strength , wear resistance and long life.
4. FRP: Taiwan imported high quality selection of synthetic resin and glass fiber mat , its high tensile strength, hardness, life is about more than 30 years , than conventional glass fiber cloth and synthetic resin fiberglass products and long service life of about 10 years.