Schneider Automation Telemecanique Modicon Quantum DDO, DDO 353 01,140DDO35301
Quick Details:
SCHNEIDER ELECTRIC
MODICON
140-DDO-353-01
140DDO35301
OUTPUT MODULE
DC OUT 24VDC
4X8 SOURCE
One Year warrabty
SPECIFICATION
Manufacturer | Schneider Electric |
Series | Modicon Quantum |
Module format | Standard |
Product or component type | Dc discrete output module |
Discrete output number | 32 |
Group of channels | 4 groups of 8 |
Discrete output logic | Positive logic (source) |
Addressing requirement | 2 output words |
Discrete output voltage | 24 V DC |
Output voltage limits | 19.2...30 V |
Absolute maximum output | 50 V for 1 s decaying pulse |
Voltage drop | 0.4 V 0.5 A |
Maximum load current | 16 A per module |
| 16 A per module |
| 4 A per group |
| 4 A per group |
Surge current | <= 2 A |
| <= 2 A |
Response time | <= 0.1 ms at state 1 to state 0 |
| <= 1 ms at state 0 to state 1 |
Leakage current | <= 1 mA 24 V |
Load inductance | Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz))) |
| Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz))) |
Fault indication | Loss of field power |
| Blown fuse |
Associated fuse rating | 3 A each point |
| 3 A each point |
| 5 A per group |
| 5 A per group |
Isolation between channels and bus | 1780 Vrms DC for 1 minute |
Isolation between group | 500 Vrms DC for 1 minute |
Protection type | Internal output protection by 5 A fuse per group |
Power dissipation | 5 W |
Marking | CE |
Local signalling | 1 LED green bus communication is present (Active) |
| 1 LED red external fault detected (F) |
| 32 LEDs green input status |
Bus current requirement | <= 330 mA |
| <= 330 mA |