Specifications
Brand Name :
Jinzhen Boiler
Model Number :
DZH2-1.0
Certification :
IS0900
Place of Origin :
China
MOQ :
1
Price :
Negotiable
Payment Terms :
L/C, T/T, Western Union
Supply Ability :
80 set per month
Delivery Time :
5-8 working days
Packaging Details :
Steam Boiler in nude package, but covered with water-proof covering, accessories in plywood case
steam capacity :
2 ton/h, 2000kg/h
Pressure :
1.0/1.25mpa
Steam Temperatur :
184/194C
Material :
Q245R Steel Plate
Type :
Natural Circulation
Usage :
Industrial
Structure :
Fire Tube
Style :
Horizontal
Thermal efficiency :
80%
Output :
steam
Suitable fuel :
wood, biomass, coal
Fuel consumption :
300kg
feed water temperature :
20C
Effective area of grate :
3.36m2
weight :
12t
size :
4.1x 2.2x 2.9
warranty :
2 year
Description

DZH Type Moving Grate Stoker Waste Palm Fired Steam Boiler For Palm Oil Mill

Model:DZH Type Moving Grate Stoker steam Boiler

Structure:WaterTube Fire Tube Three Pass

Rated Steam Capacity:1-20 ton/hr

Rated Steam Pressure:0.7/1.0/1.25/1.6/2.5 Mpa

Rated Steam Temperature:170/184/194/204/225 C

Application:Textile Mill,Food and Beverage,Chemical,Medicine,Light Industry,Rubber,Printing and Dyeing Plant,Paper Mill,Wood Processing,Garment and Laundry etc.

DZH series manual coal fired steam boiler, use movable fire grate, equip with blower, draft fan, economizer, deduster, automatic water treatment, water pump, steam header, control cabinet, valves and meters etc auxiliary machines. Due to the less of auxiliaries of this series boiler, so low fault of machines, reduce maintenance cost, easy operation, save time and materials, is an economical boiler type. Suitable for various types of coal fuels, environmental protection, price position moderate, is the first choice of small and medium enterprises who use steam for processing line.

Performance characteristics:

1. The biomass fired boiler is a horizontal fast-installed steam boiler with natural circulation of working fluid. The steam boiler heat exchange system consists of a drum, left and right headers, and water walls. The main heating surface has a water wall in the furnace, and part of the drum and the drum have convection. Tube bundle. This series of steam boilers are composed of five parts when they leave the factory: the main body of the boiler, the flue duct, the dust collector, and the piping system. The first four parts have been manufactured in the factory and can be transported to the installation site for assembly, which can be greatly shortened Installation cycle, and can guarantee the quality of product installation.

2. High-quality boiler design performance: The main heating surface of the steam boiler is made of seamless steel pipes for 20# low and medium pressure boilers, and the drum is made of special steel plates for the boiler. The left and right headers are made of seamless steel pipes.

3. The steam boiler arch is made of refractory concrete. The back arch is low and long, so it burns well. The two-wing flue and side wall bricks are made of refractory sintered bricks. The front and back walls of the boiler are made of general-purpose refractory bricks.

4. The wood steam boiler grate has reasonable air distribution, large combustion chamber, and strong applicability of coal types. It is suitable for all kinds of bituminous coal, anthracite, and mixed coal. It burns fully. Because the high-temperature flue gas enters the settling chamber, it enters the two-wing flue from both sides, The front smoke box, so the smoke and dust removal effect is good.

5. The water cycle is simple, and the structure of the pressurized parts is reasonable, and it is completely safe to operate under the condition of ensuring water quality.

6. The boiler combustion equipment is a quick-installed grate. The combustion equipment is manufactured and installed in the factory and can be directly installed on the foundation after being transported to the construction site. It has a reasonable and compact structure and low steel consumption, which makes the performance, weight and structure of the boiler Compared with domestic boilers of the same capacity, the size has obvious advantages.

Steam Boiler specification sheet

Boiler model DZH1-1.0-T DZH2-1.25-T DZH4-1.25-T DZH6-1.25-T
Rated capacity ton/h 1 2 4 6
Rated pressure Mpa 1.0 1.25 1.25 1.25
Rated steam temperature 184 194 194 194
Active grate area m2 2.11 3.95 5.34 9.2
Exhaust gas temperature 127.2 126.4 137.3 146.8
Fuel consumption kg/h 176 352 705 1058
Thermal efficiency % 83.5 83.5 83 83
Weight ton 9 15 18.5 25
Dimension mm 4320*1825*2685 4950*2650*3177 5650*2550*3434 6930*3020*3664
Delivery mode / Package Package Package Package

Fault alarm and safety protection

The control system can monitor the current working condition of the steam boiler in real time, and carry out real time and comprehensive intelligent fault identification and processing.The control system can diagnose and deal with the following faults in real time:

High steam pressure protection: when the steam overpressure in the pot, the control system immediately enters the chain, and the sound and light alarm, the screen shows "high steam pressure".After the fault is eliminated, press the reset key to remove the chain.

Water shortage protection in the boiler: when the water level of the boiler is extremely low due to the pump failure or other reasons, the control system will immediately turn off the power supply of the induced draft fan and enter the chain, and the sound and light alarm will be given, and the screen will show the water level is extremely low.After the fault is eliminated, press the reset key to remove the chain.

Boiler water level is too high: when the water level in the boiler is higher than the upper warning level, the sound and light alarm will be given."Ultra-high water level in the pot" prompts, and the display prompts drainage.Automatic recovery after fault elimination, stop the pump and keep the furnace.

Pump motor overload: heat relay action when the pump motor overflows, cut off the power supply of the pump motor and stop the pump, which is realized by hardware.

Power failure: when power failure occurs, the control system will immediately turn off the power of all equipment in the cabinet where the power failure occurs.When the power is restored, the cabinet will automatically be off duty. It is necessary to restart the machine and start all the devices to ensure the safety of the equipment.

DZH Type Moving Grate Stoker Waste Palm Fired Steam Boiler For Palm Oil Mill

Application for biomass steam boiler

Wood fired steam boiler is suitable for painting room, drying box, drying tower painting line and other purposes.It is especially suitable for central heating in urban residential areas, industrial production, enterprises and institutions, schools, hotels, bath centers and other places where heating, hot water and steam are needed.

DZH Type Moving Grate Stoker Waste Palm Fired Steam Boiler For Palm Oil Mill

Send your message to this supplier
Send Now

DZH Type Moving Grate Stoker Waste Palm Fired Steam Boiler For Palm Oil Mill

Ask Latest Price
Brand Name :
Jinzhen Boiler
Model Number :
DZH2-1.0
Certification :
IS0900
Place of Origin :
China
MOQ :
1
Price :
Negotiable
Contact Supplier
DZH Type Moving Grate Stoker Waste Palm Fired Steam Boiler For Palm Oil Mill
DZH Type Moving Grate Stoker Waste Palm Fired Steam Boiler For Palm Oil Mill
DZH Type Moving Grate Stoker Waste Palm Fired Steam Boiler For Palm Oil Mill
DZH Type Moving Grate Stoker Waste Palm Fired Steam Boiler For Palm Oil Mill
DZH Type Moving Grate Stoker Waste Palm Fired Steam Boiler For Palm Oil Mill
DZH Type Moving Grate Stoker Waste Palm Fired Steam Boiler For Palm Oil Mill
DZH Type Moving Grate Stoker Waste Palm Fired Steam Boiler For Palm Oil Mill
DZH Type Moving Grate Stoker Waste Palm Fired Steam Boiler For Palm Oil Mill

Henan Jinzhen Boiler Co., Ltd.

Active Member
7 Years
henan, zhengzhou
Since 2015
Business Type :
Manufacturer, Distributor/Wholesaler, Agent, Importer, Exporter, Trading Company, Seller
Total Annual :
500000-1000000
Employee Number :
125~150
Certification Level :
Active Member
Contact Supplier
Submit Requirement