Schneider LC1-F400 Electrical Contactor Switch LC1F400 High Current Contactors For Motor Control
Application
TeSys F is suitable for the control of all types of motors and distribution circuits across industry, infrastructure and building. Specific applications include:
TeSys F series of contactors are specifically designed for the most demanding motor and power switching applications.
TeSys F
TeSys FG range
TeSys CR1 F
Technology parameter
range | TeSys | |
---|---|---|
product name | TeSys F | |
product or component type | Contactor | |
device short name | LC1F | |
contactor application | Motor control Resistive load | |
utilisation category | AC-3 AC-4 AC-1 | |
poles description | 3P | |
power pole contact composition | 3 NO | |
[Ue] rated operational voltage | <= 1000 V AC 50/60 Hz <= 460 V DC | |
[Ie] rated operational current | 500 A (<= 40 °C) at <= 440 V AC AC-1 400 A (<= 55 °C) at <= 440 V AC AC-3 | |
motor power kW | 75 kW at 400 V AC 50/60 Hz AC-4 200 kW at 380...400 V AC 50/60 Hz AC-3 220 kW at 415 V AC 50/60 Hz AC-3 250 kW at 440 V AC 50/60 Hz AC-3 257 kW at 500 V AC 50/60 Hz AC-3 185 kW at 1000 V AC 50/60 Hz AC-3 110 kW at 220...240 V AC 50/60 Hz AC-3 280 kW at 660...690 V AC 50/60 Hz AC-3 |
[Uimp] rated impulse withstand voltage | 8 kV | |
---|---|---|
overvoltage category | III | |
[Ith] conventional free air thermal current | 500 A at <= 40 °C | |
Irms rated making capacity | 4000 A AC conforming to IEC 60947-4-1 | |
rated breaking capacity | 3200 A conforming to IEC 60947-4-1 | |
[Icw] rated short-time withstand current | 3600 A <= 40 °C 10 s 2400 A <= 40 °C 30 s 1700 A <= 40 °C 1 min 1200 A <= 40 °C 3 min 1000 A <= 40 °C 10 min | |
associated fuse rating | 400 A aM at <= 440 V 500 A gG at <= 440 V | |
average impedance | 0.26 mOhm at 50 Hz - Ith 500 A | |
[Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C | |
power dissipation per pole | 42 W AC-3 65 W AC-1 | |
mounting support | Plate | |
standards | IEC 60947-4-1 EN 60947-4-1 JIS C8201-4-1 EN 60947-1 IEC 60947-1 | |
product certifications | CB RINA UL ABS DNV RMRoS BV CSA LROS (Lloyds register of shipping) | |
connections - terminals | Power circuit : lugs-ring terminals 2 cable(s) 150 mm² Power circuit : bar 2 x (30 x 5 mm) | |
tightening torque | Power circuit : 35 N.m |
IP degree of protection | IP20 front face with shrouds (ordered separately) conforming to IEC 60529 IP20 front face with shrouds (ordered separately) conforming to VDE 0106 | |
---|---|---|
protective treatment | TH | |
ambient air temperature for operation | -5...55 °C | |
ambient air temperature for storage | -60...80 °C | |
permissible ambient air temperature around the device | -40...70 °C | |
operating altitude | 3000 m without derating | |
mechanical robustness | Shocks resistance contactor closed 15 Gn for 11 ms Shocks resistance contactor open 6 Gn for 11 ms Vibrations resistance contactor closed 5 Gn, 5...300 Hz Vibrations resistance contactor open 1.5 Gn, 5...300 Hz | |
height | 206 mm | |
width | 213 mm | |
depth | 219 mm | |
product weight | 8 kg |