SIRIUS 3RT1065-6AP36 up to 250 kW DC CONTACTOR 265A 132 kW Power CONTACTOR
Power contactor, AC-3 265 A, 132 kW / 400 V AC (50-60 Hz) / DC operation 220-240 V UC Auxiliary contacts 2 NO + 2 NC 3-pole, Size S10 Busbar connections Drive: conventional screw terminal
Overview
| | | | | |
- Standard operating mechanism with economy circuit for AC and DC operation
| S6 ... S12 | 55 ... 250 | ✓1) | ✓ | 3RT10..‑.A.36 |
- Solid-state operating mechanism
with the option of control via a separate 24 V DC control signal input | | | | | |
- Fail-safe control signal input
can be used in safety-related applications to SIL CL 3 | S6 ... S12 | 55 ... 250 | ✓1) | -- | 3RT10..‑.S.36 |
- Standard control signal input
| ✓1) | ✓ | 3RT10..‑.N.36 |
- Standard control signal input, with remaining lifetime indicator (RLT)
| ✓1) | -- | 3RT10..‑.P.35 |
3RT contactors, sizes S00 to S12
Our power range:
- Contactors for switching motors:
- Size S00: 3RT201 up to 7.5 kW
- Size S0: 3RT202 up to 18.5 kW
- Size S2: 3RT203 up to 37 kW
- Size S3: 3RT204 up to 55 kW
- Sizes S6 to S12: 3RT10 up to 250 kW
- Vacuum contactors for switching motors,
- Sizes S10 and S12: 3RT12 up to 250 kW
- Size 14: 3TF6 up to 450 kW
Standards
IEC/EN 60947‑1, IEC/EN 60947‑4‑1, IEC/EN 60947‑5‑1 (auxiliary switches)
Ambient conditions
If the devices are used in ambient conditions which deviate from common industrial conditions (IEC 60721-3-3 "Stationary Use, Weather-Protected"), information must be obtained about possible restrictions with regard to the reliability and endurance of the device and possible protective measures. In this case contact our Technical
Auxiliary contact complement
- Size S00: An auxiliary contact is integrated in the basic unit.
- Sizes S0 to S3: The basic units contain two integrated auxiliary contacts (1 NO + 1 NC).
All basic units, with the exception of coupling relays sizes S00 and S0, can be expanded using auxiliary switches. - Sizes S6 to S12: These contactors are supplied with two laterally mounted auxiliary switches. The mounting of auxiliary switches is possible on the front and on the side (the 3RT12 vacuum contactor is an exception: only lateral mounting of auxiliary switches is possible here).
For detailed information about mounting auxiliary switches, see Selection aid for mountable auxiliary switches → Assets.
Contact reliability
If voltages ≤ 110 V and currents ≤ 100 mA are to be switched, the auxiliary contacts of the 3RT contactors or 3RH contactor relays should be used as they guarantee a high level of contact reliability.
These auxiliary contacts are especially suitable for solid-state circuits with currents ≥ 1 mA at a voltage of 17 V and higher.
General technical data | Size of contactor | S10 | Product extension | | ● function module for communication | No | ● Auxiliary switch | Yes | Power loss [W] for rated value of the current | | ● at AC in hot operating state | 54 W | ● at AC in hot operating state per pole | 18 W | Power loss [W] for rated value of the current without load current share typical | 7.4 W | Surge voltage resistance | | ● of main circuit rated value | 8 kV | ● of auxiliary circuit rated value | 6 kV | maximum permissible voltage for safe isolation | | ● between coil and main contacts acc. to EN 60947-1 | 690 V | |
No-load switching frequency | |
● at AC | 2 000 1/h |
● at DC | 2 000 1/h |
Operating frequency | |
● at AC-1 maximum | 800 1/h |
● at AC-2 maximum | 300 1/h |
● at AC-3 maximum | 700 1/h |
● at AC-4 maximum | 130 1/h |
Control circuit/ Control |
Type of voltage of the control supply voltage | AC/DC |
Control supply voltage at AC | |
● at 50 Hz rated value | 220 ... 240 V |
● at 60 Hz rated value | 220 ... 240 V |
Control supply voltage at DC | |
● rated value | 220 ... 240 V |
Operating range factor control supply voltage rated value of magnet coil at DC | |
● initial value | 0.8 |
● Full-scale value | 1.1 |
Operating range factor control supply voltage rated value of magnet coil at AC | |
● at 50 Hz | 0.8 ... 1.1 |
● at 60 Hz | 0.8 ... 1.1 |
Design of the surge suppressor | with varistor |
Apparent pick-up power of magnet coil at AC | |
● at 50 Hz | 590 V·A |
Inductive power factor with closing power of the coil | |
● at 50 Hz | 0.9 |
Apparent holding power of magnet coil at AC | |
● at 50 Hz | 6.7 V·A |
Inductive power factor with the holding power of the coil | |
● at 50 Hz | 0.9 |
Closing power of magnet coil at DC | 650 W |
Holding power of magnet coil at DC | 7.4 W |
Closing delay | |
● at AC | 30 ... 95 ms |
● at DC | 30 ... 95 ms |
Opening delay | |
● at AC | 40 ... 80 ms |
● at DC | 40 ... 80 ms |
Arcing time | 10 ... 15 ms |
Control version of the switch operating mechanism | Standard A1 - A2 |
Auxiliary circuit |
Number of NC contacts for auxiliary contacts | |
● instantaneous contact | 2 |
Number of NO contacts for auxiliary contacts | |
● instantaneous contact | 2 |
Operating current at AC-12 maximum | 10 A |
Operating current at AC-15 | |
● at 230 V rated value | 6 A |
● at 400 V rated value | 3 A |
● at 500 V rated value | 2 A |
● at 690 V rated value | 1 A |
Operating current at DC-12 | |
● at 24 V rated value | 10 A |
● at 48 V rated value | 6 A |
● at 60 V rated value | 6 A |
● at 110 V rated value | 3 A |
● at 125 V rated value | 2 A |
● at 220 V rated value | 1 A |
● at 600 V rated value | 0.15 A |
Operating current at DC-13 | |
● at 24 V rated value | 10 A |
● at 48 V rated value | 2 A |
● at 60 V rated value | 2 A |
● at 110 V rated value | 1 A |
● at 125 V rated value | 0.9 A |
● at 220 V rated value | 0.3 A |
● at 600 V rated value | 0.1 A |
Contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
Connections/ Terminals |
Width of connection bar | 25 mm |
Thickness of connection bar | 6 mm |
Diameter of holes | 11 mm |
Number of holes | 1 |
Type of electrical connection | |
● for main current circuit | Connection bar |
● for auxiliary and control current circuit | screw-type terminals |
● at contactor for auxiliary contacts | Screw-type terminals |
● of magnet coil | Screw-type terminals |
Type of connectable conductor cross-sections | |
● at AWG conductors for main contacts | 2/0 ... 500 kcmil |
Connectable conductor cross-section for main contacts | |
● stranded | 70 ... 240 mm² |
Connectable conductor cross-section for auxiliary contacts | |
● single or multi-stranded | 0.5 ... 4 mm² |
● finely stranded with core end processing | 0.5 ... 2.5 mm² |
Type of connectable conductor cross-sections | |
● for auxiliary contacts | |
— solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²) |
— single or multi-stranded | 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²) |
— finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
● at AWG conductors for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14), 1x 12 |
AWG number as coded connectable conductor cross section | |
● for auxiliary contacts | 18 ... 14 |
Main models:
3RT1064-2AB36
3RT1064-2AD36
3RT1064-2AF36
3RT1064-2AM36
3RT1064-2AP36
3RT1064-2AR36
3RT1064-2AS36
3RT1064-2AT36
3RT1064-2AU36
3RT1064-2AV36
3RT1064-2NB36
3RT1064-2NF36
3RT1064-2NP36
3RT1064-6AB36
3RT1064-6AD36
3RT1064-6AF36
3RT1064-6AM36
3RT1064-6AP36
3RT1064-6AP36-1AA0
3RT1064-6AR36
3RT1064-6AS36
3RT1064-6AT36
3RT1064-6AU36
3RT1064-6AV36
3RT1064-6LA06
3RT1064-6NB36
3RT1064-6NF36
3RT1064-6NP36
3RT1064-6PF35
3RT1064-6PP35
3RT1064-6QF35
3RT1064-6QP35
3RT1065-2AB36
3RT1065-2AD36
3RT1065-2AF36
3RT1065-2AM36
3RT1065-2AP36
3RT1065-2AR36
3RT1065-2AS36
3RT1065-2AT36
3RT1065-2AU36
3RT1065-2AV36
3RT1065-2NB36
3RT1065-2NF36
3RT1065-2NP36
3RT1065-6AB36
3RT1065-6AD36
3RT1065-6AF36
3RT1065-6AM36
3RT1065-6AP36
3RT1065-6AR36
3RT1065-6AS36
3RT1065-6AT36
3RT1065-6AU36
3RT1065-6AV36
3RT1065-6LA06
3RT1065-6NB36
3RT1065-6NF36
3RT1065-6NP36
3RT1065-6PF35
3RT1065-6PP35
3RT1065-6QF35
3RT1065-6QP35
3RT1066-2AB36
3RT1066-2AD36
3RT1066-2AF36
3RT1066-2AM36
3RT1066-2AP36
3RT1066-2AR36
3RT1066-2AS36
3RT1066-2AT36
3RT1066-2AU36
3RT1066-2AV36
3RT1066-2NB36
3RT1066-2NF36
3RT1066-2NP36
3RT1066-6AB36
3RT1066-6AD36
3RT1066-6AF36
3RT1066-6AM36
3RT1066-6AP36
3RT1066-6AR36
3RT1066-6AS36
3RT1066-6AT36
3RT1066-6AU36
3RT1066-6AV36
3RT1066-6LA06
3RT1066-6NB36
3RT1066-6NF36
3RT1066-6NP36
3RT1066-6PF35
3RT1066-6PP35
3RT1066-6PP35-0SW0
3RT1066-6QF35
3RT1066-6QP35