Specifications
Brand Name :
DONGJIAXIN
Model Number :
DWZA-YJY/N2X2Y
Certification :
IEC, Rosh,CCC
Place of Origin :
CHINA
MOQ :
Negotiable
Price :
Negotiable
Payment Terms :
L/C, T/T
Supply Ability :
100KM/Week
Delivery Time :
7-15 working days
Packaging Details :
Steel wooden drum, Coil In Foil / Drum
Model name :
DWZA
Armour :
Galvanized Steel Tape
Popular Sizes :
2~5core x1.5~630mm²
insulator :
XLPE
Conductor Type :
Bare Copper Class 2
Sheath :
PVC, ZR-PVC, PE, LSOH
High Light :
low smoke halogen free cable, lszh power cables
Application :
Underground
Description

Long Life Low Smoke Zero Halogen Cable Bare Copper Class 2 Conductor

Low Smoke Halogen Free Cable

copper conductor pvc insulated steel tape armoured multi-core power cables

Construction:

Stranded (RM) bare copper as per IEC60228
Mica Tape for Fire-Proof
XLPE (cross-linked polyethylene) Insulation
Fillers strip, Yarn, or Paper
Non woven Wrapping tape or Flame Retardant

Extruded PVC Inner Covering

Galvanized Steel Tape Armoured
Overall Sheath: polyvinylchloride (PVC) or FR-PVC, PE, LSOH

Application:


Used for tall building, Hospital, Theatre, Power station, Metro Tunnel or Petrochemical Industry or other special place required for low smoke , zero halogen clean and safe cable.

Technical data:


Test voltage 0.6/1 kV [kV] 3.5 / 5 min.
Temperature range in motion -5°C till +70°C
fixed -20°C till +70°C
Operating temperature short circuit °C 250
Short circuit time max. [sec] 5
Bending radius min. x diameter 15
Flammability standard EN 60332-1-2


Standards:

IEC 60502, 60332, 60331

DIN VDE 0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)

Model Explanation:

Model Nominal Cross Section (mm2)
Single
Core
Two
Core
Three
Core
Four
Core
Five
Core
VV22 YJV22 6-400 4-300 4-300 4-300 4-300
VV32 YJV32 10-800 4-300 4-300 4-300 4-300

N2X2Y LSZH Sheath 10mm2 Low Smoke Halogen Free Cable Class 2 Conductor

Product details

XLPE Insulation Electric Wire Cable

Type Desciption Rated Voltage NO. of Cores Nomibal section(mm2) Applications
YJV YJLV Cu or Al conductor,XLPE insulated.PVC sheathed electric cable 0.6/1KV 1,2,3,4 1.5 to 400 For laying indoors and outdoors.The LV XLPE insulated power cable is used in transmission and distribution system at rated voltagae U(Um) ≤10KV.The HV XLPE insulated power cable refers to the power cable transmission between 10KV-35KV, it is often applied to the main road of power transmission. Able to bear certain traction during installation, but not external mechanical forces.
3+1 3×4+1×2.5 to 3×400+1×185
6/6kV 1,3 25 to 500
8.7/10kV 8.7/15kV 12/20kV 1 25 to 500
3 25 to 300
21/35kv 1 50 to 500
YJV22 YJLV22 Cu or Al conductor,XLPE insulated steel tape armoured PVC sheathed electric cable 0.6/1KV 3 1.5 to 400 Suitable for burying in ground, Able to bear external mechanical forces but large pulling forces.
4 4 to 240
6/6kV 8.7/10kV 8.7/15kV 12/20kV 3 25 to 300
21/35kv 3 50 to 240

Packing&Delivery:

We are capable of meeting the most strict delivery schedules according to per purchase order. Meeting the deadline is always the top priority as any delay in the delivery of cable can contribute to overall project delay and cost overrun.
Cable is supplied in wooden reels, corrugated boxes and coils. Cable ends are sealed with BOPP self adhesive tape and non-hygroscopic sealing caps to protect the cable ends from moisture. The required marking shall be printed with a weather-proof material on the outsides of drum according to customer's requirement.


▼ Cable Drum Data:

CABLE DRUMS D1=Flange Diameter(mm) W=Useful Width (mm) D2=Barrel Diameter(mm)
N2X2Y LSZH Sheath 10mm2 Low Smoke Halogen Free Cable Class 2 Conductor 1000 700 500
1100 700 550
1200 700 600
1400 750 710
1600 900 900
1800 1120 1000
2400 1150 1300

▼ Delivery Port :

N2X2Y LSZH Sheath 10mm2 Low Smoke Halogen Free Cable Class 2 Conductor N2X2Y LSZH Sheath 10mm2 Low Smoke Halogen Free Cable Class 2 Conductor N2X2Y LSZH Sheath 10mm2 Low Smoke Halogen Free Cable Class 2 Conductor
Port of Shenzhen Port of Hongkong

Port of Guangzhou

▼ Technical parameters:

1. Single Core

Cross section of conductor(mm²) Conductor structure Insulation thickness(mm) sheath thickness(mm) Approx.cable diameter(mm) Max resistance of conductor at 20℃ (Ω/km)
1×1.5 1 0.7 1.4 6.0 12.1
1×2.5 1 0.7 1.4 6.4 7.41
1×4 1 0.7 1.4 6.9 4.61
1×6 1 0.7 1.4 7.3 3.08
1×10 7 0.7 1.4 8.4 1.83
1×16 7 0.7 1.4 9.4 1.15
1×25 7 0.9 1.4 11.0 0.727
1×35 7 0.9 1.4 12.0 0.524
1×50 10 1.0 1.4 13.3 0.387
1×70 14 1.1 1.4 15.1 0.268
1×95 19 1.1 1.5 17.3 0.193
1×120 24 1.2 1.5 19.0 0.153
1×150 30 1.4 1.6 20.9 0.124
1×185 37 1.6 1.6 23.0 0.0991
1×240 48 1.7 1.7 25.7 0.0754
1×300 61 1.8 1.8 28.3 0.0601
1×400 61 2.0 1.9 31.6 0.0470
1×500 61 2.2 2.0 35.1 0.0366
1×630 61 2.4 2.2 42.1 0.0283

2. 2 Core&3 Core

Cross section of conductor(mm²) Conductor structure Insulation thickness(mm) sheath thickness(mm) Approx.cable diameter(mm) Max resistance of conductor at 20℃ (Ω/km)
2×1.5 1 0.7 1.8 10.6 12.1
2×2.5 1 0.7 1.8 11.4 7.41
2×4 1 0.7 1.8 12.4 4.61
2×6 1 0.7 1.8 13.2 3.08
2×10 7 0.7 1.8 15.4 1.83
2×16 7 0.7 1.8 17.4 1.15
2×25 7 0.9 1.8 20.6 0.727
2×35 7 0.9 1.8 22.6 0.524
2×50 10 1.0 1.8 26.2 0.387
2×70 14 1.1 1.8 29.8 0.268
2×95 19 1.1 1.9 34.0 0.193
2×120 24 1.2 2.0 37.4 0.153
2×150 30 1.4 2.2 41.2 0.124
2×185 37 1.6 2.3 45.6 0.0991
2×240 48 1.7 2.5 51.0 0.0754
2×300 61 1.8 2.6 56.0 0.0601
2×400 61 2.0 2.9 62.6 0.0470
2×500 61 2.2 3.1 70.0 0.0366
2×630 61 2.4 3.3 83.6 0.0283
3×1.5 1 0.7 1.8 11.2 12.1
3×2.5 1 0.7 1.8 12.1 7.41
3×4 1 0.7 1.8 13.2 4.61
3×6 1 0.7 1.8 14.0 3.08
3×10 7 0.7 1.8 16.4 1.83
3×16 7 0.7 1.8 18.6 1.15
3×25 7 0.9 1.8 22.0 0.727
3×35 7 0.9 1.8 24.2 0.524
3×50 10 1.0 1.8 28.0 0.387
3×70 14 1.1 1.9 32.1 0.268
3×95 19 1.1 2.0 36.4 0.193
3×120 24 1.2 2.1 40.3 0.153
3×150 30 1.4 2.3 44.3 0.124
3×185 37 1.6 2.4 49.1 0.0991
3×240 48 1.7 2.6 54.9 0.0754
3×300 61 1.8 2.7 60.1 0.0601
3×400 61 2.0 3.0 67.4 0.0470
3×500 61 2.2 3.2 75.3 0.0366
3×630 61 2.4 3.5 90.0 0.0283

3. 4 Core&5 Core

Cross section of conductor(mm²) Conductor structure Insulation thickness(mm) sheath thickness(mm) Approx.cable diameter(mm) Max resistance of conductor at 20℃ (Ω/km)
4×1.5 1 0.7 1.8 12.2 12.1
4×2.5 1 0.7 1.8 13.1 7.41
4×4 1 0.7 1.8 14.3 4.61
4×6 1 0.7 1.8 15.3 3.08
4×10 7 0.7 1.8 18.0 1.83
4×16 7 0.7 1.8 20.4 1.15
4×25 7 0.9 1.8 24.3 0.727
4×35 7 0.9 1.8 26.7 0.524
4×50 10 1.0 1.8 30.8 0.387
4×70 14 1.1 2.0 35.4 0.268
4×95 19 1.1 2.1 40.4 0.193
4×120 24 1.2 2.3 44.9 0.153
4×150 30 1.4 2.4 49.3 0.124
4×185 37 1.6 2.6 54.7 0.0991
4×240 48 1.7 2.8 61.0 0.0754
4×300 61 1.8 3.0 67.2 0.0601
4×400 61 2.0 3.3 75.3 0.0470
4×500 61 2.2 3.5 84.0 0.0366
4×630 61 2.4 3.8 100.5 0.0283
5×1.5 1 0.7 1.8 13.2 12.1
5×2.5 1 0.7 1.8 14.2 7.41
5×4 1 0.7 1.8 15.6 4.61
5×6 1 0.7 1.8 16.7 3.08
5×10 7 0.7 1.8 19.6 1.83
5×16 7 0.7 1.8 22.3 1.15
5×25 7 0.9 1.8 26.7 0.727
5×35 7 0.9 1.8 29.4 0.524
5×50 10 1.0 1.9 34.1 0.387
5×70 14 1.1 2.1 39.1 0.268
5×95 19 1.1 2.2 44.7 0.193
5×120 24 1.2 2.4 49.7 0.153
5×150 30 1.4 2.6 54.7 0.124
5×185 37 1.6 2.8 60.6 0.0991
5×240 48 1.7 3.0 67.7 0.0754
5×300 61 1.8 3.2 74.6 0.0601
5×400 61 2.0 3.5 83.4 0.0470
5×500 61 2.2 3.8 93.4 0.0366
5×630 61 2.4 4.1 111.7 0.0283

Ordering Advice:

Rated Voltage

Application Standard:IEC/BS/UL/GB

Number of Cores

Conductor Size $ Construction

Type of Insulation

Armored or unarmored. If armour, the armour type & material

The Requirement of Sheath

Length of Cable & Packing Requirement

Other Requirement

If this all seems a little too technical for you, then why not get in touch with us.We look forward to assisting you in identifying the best products for your specific application and to answer any questions you might have.

Company information:

30 years of experience in R & D, production and sales of wire and cable.

Invest 200 million to build a modern industrial park, covering an area of 65000 square meters.

Annual revenue is about 500 million US dollars.

CNAS laboratory, more than 100 testing reports.

Products are widely used in real estate, municipal, industrial support, mobile communications etc

N2X2Y LSZH Sheath 10mm2 Low Smoke Halogen Free Cable Class 2 Conductor

N2X2Y LSZH Sheath 10mm2 Low Smoke Halogen Free Cable Class 2 Conductor

IEC, Rosh,CCC
Send your message to this supplier
Send Now

N2X2Y LSZH Sheath 10mm2 Low Smoke Halogen Free Cable Class 2 Conductor

Ask Latest Price
Watch Video
Brand Name :
DONGJIAXIN
Model Number :
DWZA-YJY/N2X2Y
Certification :
IEC, Rosh,CCC
Place of Origin :
CHINA
MOQ :
Negotiable
Price :
Negotiable
Contact Supplier
video
N2X2Y LSZH Sheath 10mm2 Low Smoke Halogen Free Cable Class 2 Conductor

SHENZHEN DONGJIAXIN WIRE&CABLE CO.,LTD

Verified Supplier
5 Years
guangdong, shenzhen
Since 1990
Business Type :
Manufacturer
Total Annual :
230701800.00-307602400
Employee Number :
200~300
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement