Emerson DeltaV™ DO 24 V DC High Side CHARM 200 mA Current Limiting Circuit, Field wiring disconnect
Device Type | 24 V DC Solenoid coils |
On State Output rating | 100 mA continuous @ 24 V DC |
Off-state Leakage Current | 1 mA maximum |
Line Fault Detection | Guaranteed short circuit: <50 Ω Load, Guaranteed good status: 240 Ω to 10 kΩ load, Guaranteed open circuit: >20 kΩ load |
Configurable Output Behavior | Momentary Output, Continuous Pulse Output, Line fault testing |
Line Fault Test Timing | 200 µsec |
Field Circuit Protection | 200 mA Current Limiting Circuit, Field wiring disconnect |
CHARM power req. | 116 mA max @ 24 V DC - Standard Terminal Block, 24 mA max @ 24 V DC - Relay Output Terminal Block |
CHARM Heat Dissipation | Pulse Count - Pulse train 0.1 Hz to 10 KHz, 50 µsec min pulse width |
Easily apply security using DeltaV built-in security features
The DeltaV control network architecture creates a separate control system network completely segmented from other networks in the plant, delivering a system inherently protected from unauthorized external access.
Reduce implementation effort with no-hassle security solutions
DeltaV Smart Switches provide auto port lockdown to prevent unauthorized access to the network from switch ports.
Monitor and manage network devices within the DeltaV system
All routine system maintenance and troubleshooting is done from secured DeltaV workstations so physical access to equipment is not required.
Improve system availability and reduce troubleshooting efforts
All network equipment supplied with the DeltaV system is fully tested and supported by Emerson as part of DeltaV development.
Easily integrate data The DeltaV DCS simplifies data integration …
• At the device level: Plug-and-play capabilities exist for runtime and diagnostics in a variety of standard protocols.
• To enterprise business systems: Connect via industry standard OPC along with built-in Service-Oriented Architecture (SOA) web services that provide connections to Emerson’s Manufacturing Execution System, Syncade™, and other systems.
• Between the field and business systems: Connections are made with minimal setup time. Decision makers at every level in the plant can get the critical data they need, reliably, securely, and in real time.