Indoor Single-Phase Single-Phase Metallic Coating Touch Proof Type MV Voltage Transformer
1. Introduction:
Voltage transformer adopts fully enclosed casting insulation structure, which encloses the primary and secondary winding and the toroidal core in the epoxy resin casting body to improve the filterability and moisture resistance. The product plug part is designed to conform to the B type inner cone (EN 50181). The overall structure is designed to be fully shielded surface. It is used indoor for measuring voltage, electric energy and protective relaying in single-phase or three-phase AC circuit with the frequency 50Hz or 60Hz and highest voltage for equipment 36kV.
2. Technical Data:
Installation site: Indoor
Rated frequency: 50/60Hz
Load power factor: cosΦ=0.8 (lagging)
Technical standard accords with: IEC 60044-2
IEC 61869-1&3
3. Specification:
Item | Specification | Unit | Data | Remarks |
1 | Um | kV | Up to 36 | |
2 | Rated Insulation Level | kV | Up to 36/70/170 | |
3 | Rated Primary Voltage | V | 33000/√3 22000/√3 11000/√3 | |
4 | Rated Secondary Voltage | V | 110/√3 or 110/3 |
Model | Rated Primary Voltage (KV) | Rated Secondary Voltage (KV) | Accuracy Classes combination | Rated output (VA) | Thermal Limiting Output (VA) | BIL (KV) |
JDZX11-12/24/36PC | 11/√3 22/√3 33/√3
| 0.11/√3 | 0.2 | 25 | 300 | 12/28/75
24/50/125
36/70/170 |
0.5 | 50 | |||||
1 | 80 | |||||
0.11/√3/0.11/3 | 0.2/6P (3P) | 25/50 | 150 | |||
0.5/6P (3P) | 50/50 |
Note:Other specifications can be designed as customized.
Outline Drawing:unit/mm
Note: Other specifications can be designed as customized.
Outline drawing: