Epoxy Resin Type Double Cable Cores Type LV Current Transformer for GIS
1. Product Introduction:
LDS235 adopts newly high permeability core with high measuring accuracy. Secondary winding fully enclosed vacuum casting in anti flaming plastic shell. It easily installed by making the primary cable through the whole, applied to electrical system cable with highest equipment voltage 0.72, functioning as the tool of current metering , signal collection, relay protection. The current transformer can be executed according to the standard IEC 61869-1:2007 and IEC 61869-2:2012. Or IEC60044-1
2. Technical Data:
1. Rated secondary current: 5A
2. Power frequency withstand voltage: 3kV
3. Rated frequency : 50/60Hz
4. Installation site: Indoor
5. Technical standard: IEC60044-1(IEC61869-1&2)
3. Specification
Model | LDSC55-35P235 | ||||||
Purpose | Measuring current transformer | Protective current transformer | Double winding current transformer | ||||
Rated transformation ratio(A) | COSΦ=0.8 Accuracy class and rated burden(VA) | ||||||
0.2S | 0.5 | 10P20 | 0.2S | 10P20 | |||
100/5 | 2.5 | 5 | 5 | 2.5 | 5 | ||
150/5 | 3.75 | 5 | 5 | 3.75 | 5 | ||
200/5 | 5 | 7.5 | 10 | 5 | 10 | ||
300/5 | 7.5 | 10 | 10 | 7.5 | 10 | ||
400/5 | 10 | 15 | 15 | 10 | 15 | ||
500/5 | 15 | 15 | 15 | 15 | 15 | ||
600/5 | 15 | 15 | 15 | 15 | 15 |