12kV Indoor Single-Phase epoxy resin type Type MV Voltage Transformer
1. Introduction:
Unshielded top busbar connector is widely used in the switchgear busbar connection system, mainly T-joint,
cross connector, shield bus composition, to achieve a fully insulated switchgear, fully sealed connection,
completely avoid the high pressure exposed in bad weather Brought about by the fatal flaws, and the
installation is simple, high reliability.
The product interface conforms to the standard N50180 -50181 C-type bushing design
2. Technical Data:
Item | Parameters |
Voltage Class | 15 kV |
Rated Current | 630 A |
AC Withstand Voltage 1 min | 42 kV |
Partial Discharge | 15 kV, ≤10 pC |
BIL | 75 kV |
Screen Resistance | ≤ 5000Ω |