Separable Connectors--Cable Connector 600A, 15 kV and 25 kV Class Insulated Cap
Application
Chuangyin® Insulated Cap is widely applicable for terminating and insulating energized bushings, including bushing inserts, loadbreak junctions, feed-thru inserts, etc. in 200 A power network.
The interface complys with IEEE standard 386, 8.3/14.4 kV and 15.2/26.3 kV, 600 A deadbreak design.
Features
Made of high quality EPDM rubber
Fully shielded, insulated and submersible
Terminating and insulating cap 15 kV and 25kV 200 A energized interfaces
100% factory tested
In compliance with IEC standard 386
Construction
1. Operating Eye
2. Insulating Layer
3. Semi-conducting Shield
4. Bolt
5. Grounding Tab
Technical Data
Voltage Class | 15 kV | 25 kV |
Voltage Rating | 8.3/14.4 kV | 15.2/26.3 kV |
Rated Current | 600 A | 600 A |
AC Withstand Voltage 5min | 39 kV | 54 kV |
DC Withstand Voltage 15min | 35 kV | 48 kV |
Partial Discharge | 15 kV, ≤10 pC | 20 kV, ≤10 pC |
BIL | 95 kV | 125 kV |
Thermal Current | 23 kA, 2 s | 23 kA, 2 s |
Dynamic Current | 84 kA, 10 ms | 84 kA, 10 ms |
Kit Contents
Insulated Cap
Wipers
Silicone Grease
Installation Tools
Installation instruction
Certificate
Ordering Instructions
Product | Part Number |
15kV, 600A Insulated Cap | CYS-A(S)JM-15/600 |
25kV, 600A Insulated Cap | CYS-A(S)JM-25/600 |